Figure 6.11, Grounding terminal location, Figure 6.12 – AERCO KC1000 Heater w/Mod-Box Controller User Manual

Page 39: Burner disassembly diagram, Figure 6.13, Exhaust sensor connector location, Figure 6.14, Blower proof switch wire locations, Maintenance

Advertising
background image

MAINTENANCE

34

Figure 6.11

Grounding Terminal Location

9. Loosen the hose clamp at the air/fuel valve

outlet and slide the clamp back towards the
burner, (see Fig. 6.12).


10. Using a 1/2” socket wrench remove six 5/16-

18 hex nuts supporting the burner, (see Fig.
6.12).

Figure 6.12

Burner Disassembly Diagram

11. Lower the burner while sliding the air hose

off the air/fuel valve. Remove the burner
through the rear of the unit.

12. Disconnect the exhaust temperature sensor

by unscrewing it from the exhaust manifold,
(See Fig. 6.13).

Figure 6.13

Exhaust Sensor Connector Location

13. Disconnect the air/fuel valve wire harness,

the 12 pin connector, from the control panel.


14. Disconnect wires #24 and #17 from the

blower proof switch (See Fig. 6.14).

Figure 6.14

Blower Proof Switch Wire Locations

15. Loosen the hose clamp on the air/fuel valve

inlet and slide the clamp back towards the
blower, (See Fig. 6.15).

Advertising