Step 5—FINAL WIRING

Bring all damper and sensor wires together at the Infinity Damper
Control. Make all system wiring connections as indicated in Fig. 9.
The two ABCD bus connections on the Infinity Damper Control

are in parallel with each other. Use either terminal block to connect
the Zoning User Interface, Smart Sensor(s), variable-speed indoor
unit and 2-speed communicating outdoor unit (if applied). If more
than four zones are required (up to 8 zones maximum), see
Step—6 and Fig. 10 for Additional Damper Control Board Setup
for Zones 5-8.

VENTILATOR WIRING — The Infinity Damper Control can
control a Carrier Heat Recovery Ventilator or Energy Recovery
Ventilator (HRV / ERV). Connect the four wires from the
ventilator control board (see ventilator installation instructions for
details) to the connector labeled (YRGB). This label identifies the
color of the wire to match the ventilator wire colors (Y=yellow,
R=red, G=green, B=blue or black). If you have two Infinity
Damper Controls, connect the ventilator to the control for zones 1
through 4.

LEAVING AIR TEMPERATURE / HEAT PUMP TEM-
PERATURE (LAT/HPT) SENSORS
— These inputs on the
Infinity Damper Control are used only for diagnostic purposes and

SET SCREW

MOUNTING HUB

ANTI-ROTATION
MOUNTING SCREW

3/16"

GAP

D

AMPER

3/16"

GAP

SET SCREW

MOUNTING HUB

ACTUATOR
HOUSING

QUICK BLADE
RELEASE

(CLS) CLOSED
(COM) COMMON
(OPN) OPEN

ANTI-ROTATION
MOUNTING SCREW (5/16")

PLASTIC COVER

CLS COM OPN

CLS

COM

OPN

Fig. 1 — Damper 24-vac Connections

C03024

/

STEEL STRAP

1

2

Fig. 2 — Insulated Round Metal Duct Work

A95130

DRIVE

ZONE
DAMPER

S-LOCK

SUPPLY
AIR DUCT

Fig. 3 — Rectangular Metal Duct Work

A92478

1 / " TO 2"

INSULATION

1 2

Fig. 4 — Insulated Rectangular Metal Duct Work

A95131

FLEXIBLE

DUCT

ZONE

DAMPER

Fig. 5 — Round Flexible Duct Work

A95132

/

STEEL STRAP

1 2

Fig. 6 — Insulated Round Flexible Duct Work

A95133

ZONE
DAMPER

2

TO 3

FIBROUS
GLASS
DUCTWORK

FIELD
SUPPLIED
SCREWS

Fig. 7 — Rectangular Fibrous Glass Duct Work

A92480

1 /

TO 2

INSULATION

1 2

Fig. 8 — Insulated Rectangular Fibrous Glass Duct

Work

A95134

4

Advertising