Zones 5 - 8, Zoning system wiring diagram, Zones 1 - 4 – Carrier Infinity SYSTXCC4ZC01 User Manual

Page 6: Fig. 9 — system wiring

Advertising
background image

Zoning System Wiring Diagram

Yellow

Green

OFF

A B C D

CLS1
COM1
OPN1

LAT COM HPT

Y R G B

ZS1
ZS1C

ZS2
ZS2C

ZS3
ZS3C

ZS4
ZS4C

CLS2
COM2
OPN2

CLS3
COM3
OPN3

CLS4
COM4
OPN4

Zone-1
Damper

Optional
Zone-1
Sensor _

Zone-2
Sensor

Zone-3
Sensor

Zone-4
Sensor

Zoning User Interface &

Smart Sensor(s)

Connection

A B C D

Y R G B

Indoor

Unit

A B C D

A B C D

2-spd.

Outdoor

Unit

A B C D

Ventilator

Unit

Optional -
Leaving Air & Heat Pump
Temperature Sensor

See Note _

Notes:
_ ABCD CONNECTORS ARE IN PARALLEL WITH EACH OTHER. USE EITHER TERMINAL BLOCK FOR ANY ABCD CONNECTION.

_ INSTALLING ZONE-1 REMOTE ROOM SENSOR WILL OVERRIDE USER INTERFACE TEMPERATURE SENSOR.

Zone-2
Damper

Zone-3
Damper

Zone-4
Damper

Status LEDs

DIP Switch

Zones 1 - 4

Damper Control Module, Zones 1 - 4

ABCD Connection:
A = Green:

RS485+

B = Yellow:

RS485-

C = White:

24VAC (COM)

D = Red:

24VAC (HOT)

Dampers:
CLS_

= Close

COM_ = Common
OPN_ = Open

F U S E

1 2

ON

Fig. 9 — System Wiring

A03161

Zoning System Wiring Diagram

Yellow

Green

A B C D

CLS1
COM1
OPN1

LAT COM HPT

Y R G B

ZS1
ZS1C

ZS2
ZS2C

ZS3
ZS3C

ZS4
ZS4C

CLS2
COM2
OPN2

CLS3
COM3
OPN3

CLS4
COM4
OPN4

Zone-5
Damper

Zone-5
Sensor

Zone-6
Sensor

Zone-7
Sensor

Zone-8
Sensor

Connect to Zones 1-4

Damper Control

Module

A B C D

A B C D

See Note _

Zone-6
Damper

Zone-7
Damper

Zone-8
Damper

For Zones 5-8, a second Damper

Control Module must be applied

ON = Zones 5-8

Notes:
_ FOR ZONES 5 THROUGH 8: A SECOND DAMPER CONTROL MODULE IS REQUIRED. BUS CONNECTION
ABCD MUST BE CONNECTED BETWEEN BOTH DAMPER CONTROL MODULES.

_ SET BOTH DIP SWITCH POSITIONS TO ON (right position) AT SECOND MODULE ONLY TO ACTIVATE ZONES 5-8.

Zones 5 - 8

Damper Control Module, Zones 5 - 8

No Connection

ON

DIP Switch

Dampers:
CLS_

= Close

COM_ = Common
OPN_ = Open

F U S E

1 2

ON

Fig. 10 — Additional Damper Control

Board Setup for Zones 5 - 8

A03162

6