3.4

ELECTRICAL CONNECTIONS:

WARNING:

ELECTRICAL HAZARDS

Before proceeding read Section 1-1 on Electrical Safety. Failure to
follow the instructions in Section 1-1 could result in serious personal
injury, death and/or property damage

3.4.1

POWER SUPPLY / BRANCH CIRCUIT

WARNING:

POWER SUPPLY INCOMPATIBILITY HAZARD

Check power supply to make certain that voltage, frequency and
current carrying capacity are in accordance with the motor
nameplate. Failure to match motor nameplate values could result in
serious personal injury, death and/or property damage

WARNING:

BRANCH CIRCUIT SUPPLY HAZARD

Motor and control wiring, fusing, overload protection, disconnects,
accessories and grounding must always conform to the applicable
electrical codes as well as local codes and sound practices.

3.4.1.1

Branch Circuit Supply

to a motor should include a

disconnect switch, short circuit current fuse or breaker protection,
motor starter (controller) and correctly sized thermal elements or
overload relay protection.

3.4.1.2

Fuses, Breakers, Overload Relays

Short Circuit Current Fuses or Breakers are for the protection of the
branch circuit. Starter or motor controller overload relays are for the
protection of the motor. Each of these should be properly sized and
installed per the applicable electrical codes as well as local codes
and practices.

WARNING:

PROTECTIVE DEVICE DISABLED HAZARD

DO NOT bypass or disable protective devices. Protection removal
could result in serious personal injury, death and/or property
damage

3.4.1.3

AC Power Supply Limits

Motors are designed to operate within the following limits at the
motor terminals:
1-

AC power is within +/- 10 % of rated voltage with rated

frequency applied. (Verify with nameplate ratings) OR
2-

AC power is within +/- 5% of rated frequency with rated voltage

OR
3-

A combined variation in voltage and frequency of +/- 10% (sum

of absolute values) of rated values, provided the frequency variation
does not exceed +/-5% of rated frequency.
4-

For 3 phase motors the line to line full load voltage must be
balanced within 1%.

5-

If the motor is rated 208-230V, the voltage deviations must be
calculated from 230V.

CAUTION:

Reduced Motor Performance

Operation outside of these limits will degrade motor performance
and increase operating temperature.

3.4.2

TERMINAL BOX

:

3.4.2.1

Conduit Opening:

For ease of connections,

motors are typically provided with large terminal boxes. Most motors
have conduit access in 90 degree increments, the terminal box
conduit opening is typically provided via knockouts, holes with
covers, or the terminal box is rotate-able. Fabricated conduit boxes
may have a removable plate for the installer to provide correctly
sized hole(s).

3.4.2.2

Hazardous Locations Motors:

WARNING:

EXPLOSION HAZARDS

(1) Terminal Boxes mounted to motor with a pipe nipple: If a
pipe nipple mounted terminal box is removed or rotated it must be
reassembled with a minimum of five full threads of engagement.
(2) Component Removal: Do not set a terminal box component on
its machined surfaces. Prior to component reassembly wipe clean
all machined surfaces.

(3) Machined Surface Gap (Hazardous Locations Terminal
Boxes): The gap between mating surfaces with the machined
terminal box MUST BE LESS THAN 0.002 inches. This gap must
be checked with a feeler gage along the entire perimeter. If there is
visible damage to the mating surfaces, or if the gap between these
surfaces exceeds 0.002 inches, DO NOT complete the installation
and contact the motor manufacturer. Failure to follow these
instructions could result in serious personal injury, death and/or
property damage

3.4.3

LEAD CONNECTIONS

Electrical connections to be made per nameplate connection diagram
or separate connection plate.

In making connections follow the

applicable electrical code as well as local codes and practices.

WARNING:

ELECTRICAL CONNECTION HAZARD

Failure to correctly connect the motor leads and grounding
conductor can result in injury or death. Motor lead connections can
short and cause damage or injury if not well secured and insulated.

3.4.3.1 Wire Size (Single Phase) Requirements

The minimum wire size for Single Phase, 115 & 230 Volt Circuits
must meet table 3-8 for a given distance between motor and
either Fuse or Meter Box.

Table 3-8 Minimum Wire Gage Size Single Phase
115 & 230 Volt Circuits

Distance (Feet) - Motor to Fuse or Meter Box

Motor

100 Ft.

200 Ft.

300 Ft.

500 Ft.

HP

115

230

115

230

115

230

115

230

1/4

14

14

10

12

8

10

6

8

1/3

12

14

10

12

6

10

4

8

1/2

10

12

8

10

6

8

4

6

3/4

10

12

6

10

4

8

2

6

1

8

10

6

8

4

6

4

1 1/2

4

10

0

8

6

4

2

8

6

4

2

3

8

6

4

2

5

6

4

2

0

3.4.3.2 Extension Cords (Single Phase Motors):

Where an extension cord(s) is utilized to provide power to the
motor the extension cord(s) must be…(1) the proper gauge size
per table 3-8, (2) in good working condition (3) properly
grounded.

3.4.4

GROUND CONNECTION(S):

WARNING:

ELECTRICAL GROUNDING HAZARD

For general information on grounding (USA) refer to NEC Article 250.
Improper grounding of an inverter fed motor may result in frame
voltages in excess of 500 Volts. In making the ground connection,
the installer must make certain that a good electrical connection is
obtained between motor and grounding lead. Failure to properly
ground motors, per the applicable national code (such as NEC Article
430) and local codes may cause serious injury or death to personnel.

Primary “Internal” Ground: A grounding conductor must be
connected to the grounding terminal provided in the terminal housing.
This grounding terminal is either a ground screw, ground lug, or a
tapped hole to be used with a separately provided ground screw. The
internal grounding feature is accessible inside the terminal housing
and must be used as the primary grounding connection.
Secondary “External” Ground: Some motors are provided with a
supplemental grounding terminal located on the external surface of
the motor frame or feet. This external terminal is for supplemental
bonding connections where local codes permit or require such
connection

3.4.5

START UP:

WARNING:

ELECTRICAL SHOCK HAZARD:

Be certain that all connections are secure and the conduit box cover
is fastened in place before electrical power is connected. Failure to
follow these instructions could result in serious personal injury, death,
and/or property damage.