TYPICAL THERMOSTAT INTERFACE

1. If ‘W’ is ON, then ‘FR’ is forced ON (regardless of ‘G’) & ‘CR’ is forced OFF.
2. If ‘Y’ is ON, then ‘FR’ is forced ON (regardless of ‘G’).
3. If IFT (indoor coil) is < 35° F, then ‘CR’ is forced OFF until IFT is > 39° F.

T’STAT OUTPUT:

RC CONTROLER OUTPUT:

UNIT OPERATION:

‘G’ — 24 VAC
‘G’ — 0 VAC

‘FR’ — LINE VAC
‘FR’ — 0 VAC

FAN

‘Y’ — 24 VAC
‘O’ — 0 VAC

‘HR1 & HR2’ — LINE VAC
‘RVR’ — LINE VAC

HEATING

‘W’ — 24 VAC

‘HR1 & HR2’ — LINE VAC

HEATING

‘Y’ — 24 VAC
‘O’ — 24 VAC

‘CR’ — LINE VAC
‘RVR’ — 0 VAC

COOLING

‘R’ — 24 VAC
‘C’ — COMMON

‘R’ — 24 VAC OUTPUT
‘C’ — COMMON

POWER TO WALL
THERMOSTAT

NOTES:

1. Recommended for use on grounded power supply only.
2. Compressor and fan motor thermally protected.
3. Use copper conductors only.
4. All wiring must conform with NEC and local codes.
5. Dashed lines indicate components when used.
6. Field control wire suitable for NEC class 2 control circuit, at

24 volts.

7. OFT determines whether to bring on compressor heat or

electric heat.

FIGURE 69 — 52CQ AND 52 PQ — TYPICAL WIRING SCHEMATIC FOR

WALL THERMOSTAT HEAT PUMP UNITS

Component Connection (Marked)

Component Connection (Unmarked)

Terminal Board Connection

Field Splice

Field Control Wiring

Accessory or Optional Wiring

To Indicate Common Potential Only
Not To Represent Wire

CAP

—

Capacitor

COMP

—

Compressor

FM

—

Fan Motor

COMPONENT LEGEND

HTR

—

Heater

IFT

—

Indoor Frost Thermostat

NEC

—

National Electrical Code

OFT

—

Outdoor Frost Thermostat

OL

—

Overload

PCBD

—

Printed Circuit Board

HR1

—

Heater Relay

HR2

—

Heater Relay

CR

—

Compressor Relay

FR

—

Fan Relay

RVR

—

Reversing Valve Relay

PLS

—

Primary Limit Switch

RVS

—

Reversing Valve Solenoid

SLS

—

Secondary Limit Switch

SSS

—

Speed Selector Switch

ST

—

Start Thermistor

TRANS

—

Transformer

Advertising
This manual is related to the following products: