Wiring Terminations for models 6300 and 6400

Terminal

Function

Description

H

Output

Humidifier (6400 Only)

A / D *

Output

(A) Economizer Control, (D) Dehumidifier

G

Output

Fan Control

Rc

Input

24 Volt AC Cooling Transformer

(Dual Transformer Systems Only)

Rh

Input

Power Connection (24 Volt AC Heating

Transformer or Millivolt Power Source)

W1 / E /

Output

(W1) 1st Stage Conventional Heat,

AUX1

(E) Emergency Heat,

(AUX1) 1st Stage Auxiliary Heat

W2 / AUX2

Output

(W2) 2nd Stage Conventional Heat,

(AUX2) 2nd Stage Aux Heat

W3 / O or B

Output

(W3) 3rd Stage Conventional Heat,

(O) Cool Active Reversing Valve

(B) Heat Active Reversing Valve

Y1

Output

1st Stage Compressor

Y2

Output

2nd Stage Compressor

C

Input

24 Volt AC Transformer Common

L

Input

System Malfunction Indicator

S1
S2

* This terminal appears as A on the 6300 and A/D on the 6400.