Conventional systems – Braeburn 2220NC User Manual
Page 5
 
4
1 HEAT / 1 COOL Single or Dual Transformer
Set Installer Switch to CONV
 Rh 24	Volt	AC	Power	(heating	transformer)	[note 2]
 Rc 24	Volt	AC	Power	(cooling	transformer)	[note 2]
 W1	 Heat	Relay	(appears	as	W1/E	on	2220NC)
 Y1	 Compressor	Relay
 G	 Fan	Relay
 C	 24	Volt	AC	Transformer	Common	[note 1, 3]
Typical Wiring Configurations
NOTE: The “Installer Switch” option will be configured in the next step.
Conventional Systems
24VAC Power 
Terminal (C)
NOTES - Conventional Systems
[1]	If	batteries	are	installed	the	24	Volt	AC	common	connection	is	optional
[2]	Remove	factory	installed	jumper	for	dual	transformer	systems
[3]	In	dual	transformer	systems,	transformer	common	must	come	from		
	
cooling transformer
[4] If needed for system
Provide disconnect and overload protection as required.
2 HEAT / 1 COOL Single or Dual Transformer (2220NC Only)
Set System Type to CONV
Rh
24 Volt AC Power (heating transformer)
[note 2]
Rc
24 Volt AC Power (cooling transformer)
[note 2]
W1
Heat Relay Stage 1
W2
Heat Relay Stage 2
Y1
Compressor Relay Stage 1
G
Fan Relay
C
24 Volt AC Transformer Common
[note 1, 3]
Heat Only or Millivolt
Set Installer Switch to CONV
Rh Power Connection
W Heat Relay (appears as W1/E on 2220NC)
G Fan Relay [note 4]
C 24 Volt AC Transformer Common [note 1]