Braeburn 3220 Installer Guide User Manual

Page 10

Advertising
background image

No. Installer Setting

Factory

Setting

Comments

(

Notes follow this table)

Default

Options

(More information follows this table)

11 Compressor Power Outage

oF CPOP

oF CPOP

Disables Power Outage Lockout Delay

Protection

[notes 3, 5]

on CPOP

Enables Power Outage Lockout Delay

12 AC Power Interrupt

AC oF MONR AC oF MONR Disables AC Power Interrupt Warning

Warning

[note 5]

AC on MONR Enables AC Power Interrupt Warning

13 Compressor Short

5 CSCP

5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,

Cycle Protection

[note 6]

0 CSCP

4, 3, 2 or 0 minutes

14 Residual Cooling

60 FAN

90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,

Fan Delay

[note 6]

or

0 FAN

30 or 0 seconds.

15 Indoor Remote Sensor

I SENS

I SENS

Temperature is sensed from thermostat only.

Control*

[note 7]

E SENS

Temperature is sensed from remote sensor only.

A SENS

Temperature is combined with the thermostat and

the remote sensor.

16 Lockout Security Level

2 LOCK

2 LOCK

If locked – Complete lockout is enabled

1 LOCK

If locked – Partial lockout is enabled (SpeedBar

®

is

still functional)

17 Auto Changeover

3 BAND

2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F

Dead Band

[note 8]

BAND

(1°, 2° or 3° C) for Auto Changeover mode.

18 Compressor Balance

NO BALC

NO BALC

Disables Balance Points

Point

[notes 3, 9]

15-50 BALC Select a Compressor Balance Point of 15°- 50°F

(-9°-10° C)

19 Auxiliary Heat Balance

NO BALA

NO BALA

Disables Balance Points

Point

[notes 3, 9]

70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F

(21°- 4° C)

20 Heat Set Point Upper Limit

90LIM

90-60 LIM Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)

21 Cool Set Point Lower Limit

45LIM

45-80 LIM Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)

[note 6]

*When a Braeburn

®

outdoor sensor is connected, the thermostat automatically recognizes it. Press

BACK

and

NEXT

at the same

time to display outdoor temperature.

NOTE: Additional options such as Service Monitors, Setting the lock code, etc. are located in the User Settings –

See User manual for information on setting these options.

NOTES - Installer Settings

1 Only available if a 2 or 3 stage system type was selected in option 3.
2 Only available if a Conventional system was selected in option 3.
3 Only available if a 2 or 3 stage Heat Pump system was selected in option 3.
4 Only available if a Heat Pump system was selected in option 3.
5 Only available if the 24 Volt AC common wire is connected to the C terminal.
6 Not available if a Heat Only Hydronic system is selected in option 3.
7 Only available if a Braeburn

®

indoor remote sensor was connected.

8 Only available if auto changeover was enabled in option 2.
9 Only available if a Braeburn outdoor sensor was connected.

Detailed Explanation of Installer Settings (also see NOTES above):

1 Temperature Scale – Selects a temperature scale of either °F or °C.

2 Auto Changeover – Selects auto changeover on or off. When auto changeover mode is enabled and

selected, the system automatically switches between heating and cooling modes. There is a 5 minute delay

when switching from heating to cooling or cooling to heating in auto changeover mode.

NOTE: Also see “Auto Changeover Dead Band” in option 17.

Installer Guide 10