Dust collector controls, Ifcb, Features – CAMCORP Baghouse Collector User Manual

Page 34: Operating logic, Programming, Test & default modes

Advertising
background image

AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com

IFCB

DUST COLLECTOR CONTROLS

AC Input, Pulse Cleaning of
Bag House Dust Collectors

Models DNC-T2003 through DNC-T2032

FEATURES

Universal voltage input: 95 to 265 VAC
50/60 Hz

One SKU: covers all voltages and time
ranges required in your application

Advanced surface mount component
technology:
extremely reliable and trou-
ble free operation

Digital microprocessor controlled cir-
cuitry:
for precise pulse timing

Non-Volatile memory: for retaining pro-
grammed settings

3 digit, 7 segment numeric display: for
ease of viewing controller operation

Easily programmable: on/off times and
last output used via keypad

Small footprint: same size for 3, 6 and
10 output control

Time Ranges for all applications: On
Time: 50ms to 600 sec, Off time:
1 to
999 sec

2 modes of operation: can be operated
continuously or on demand via external
pressure switch

Finger safe terminations: reliable elec-
trical connections and increases safety

RoHS construction: suited for global
applications

Supplied on metal chassis: for mount-
ing directly in a NEMA 4 box

Retrofit models available: for direct
drop in replacement of former product

UL/CUL: File # E65038

OPERATING LOGIC

The DNC-T2003 through DNC-T2032 con-
trols are output sequencers with an ad
justable ON TIME, OFF TIME, and LAST
OUTPUT. Upon application of power to
the L1 and L2 terminals with the high pres-
sure switch co ntacts c losed, the OFF
TIME is initiated. At the end o f the preset
OFF TIME, output 1will turn on for the pre-
set ON TIME. The control will cycle through
all selected outputs until the high and low
pressure switch contacts are opened. If
the pressure switch contacts open dur-
ing the ON TIME, the output will complete
the active ON cycle. The next time the high
pressure switch is closed the next output in
the sequence is fired. Pressure monitoring
with no hysteresis is achieved by using only

a high pressure switch. Placing a jumper
across the high pressure input forces the
control to run continuously.

Note: Controls are shipped with jumper across pressure switch
terminals

PROGRAMMING

Programming is accomplished using 3
buttons:
down, up, and select
Down: Decrements the active parameter
Up: Increments the active parameter
Select: Toggles amongst the adjustable
parameters: on-time, off-time, and last
output
Programming Mode Timeout: 60 seconds

TEST & DEFAULT MODES

Test mode is entered by pressing and hold-
ing the select button for 3 seconds while the
unit is in the normal operating mode. Once
in test mode, the display will show tSt.
Pressing the up or down arrow buttons
toggles amongst outputs, and pressing
select pulses the selected output for the
preset ON-TIME. Pressing the select button
while the display shows tSt will change the
display to “dFt”. While the display shows
“dFt”, the up and down arrows toggle
amongst “y”, “n”, and “dFt”. Pressing select
when the message is “y” will set all ad just-
able parameters to the factory defaults. At
any time in test and default modes, pressing
and holding the select button for 1.5 sec-
onds will revert the controller back to the
normal operating mode.

Timer No. 1

Pressure

Switch

Note: Must
connect L1 of
first unit to L1 of
second unit.
Same with L2.

Outputs 10

HI CM LO

HI CM LO

Timer No. 2

Pressure

Switch

Outputs 10

Last
output
used

Last
output
used

Last

Solenoid

120 VAC

Last

Solenoid

Latch

Latch

120 VAC

Alternate — Action

Latching Relay

S

S

“A”

“A”

“B”

“B”

L1L2

L1L2