Installation step 1 — check jobsite, Caution – Carrier AQUAZONE 50VS User Manual

Page 2

Advertising
background image

2

INSTALLATION

Step 1 — Check Jobsite —

Installation, operation and

maintenance instructions are provided with each unit. Before

unit start-up, read all manuals and become familiar with the

unit and its operation. Thoroughly check out the system before

operation. Complete the inspections and instructions listed

below to prepare a unit for installation. See Table 1 for unit

physical data.

The 50VS units are designed for indoor installations. Units

are typically installed in a floor-level closet or a small mechan-

ical room. Be sure to allow adequate space around the unit for

servicing. See Fig. 1-5 for unit dimensions.

Table 1 — Physical Data — 50VS Unit

LEGEND

IMPORTANT: This equipment is designed for indoor

installation ONLY. Extreme variations in temperature,

humidity and corrosive water or air will adversely affect

the unit performance, reliability and service life.

CAUTION

To avoid equipment damage, do not use units as a source of

heating or cooling during the construction process. The

mechanical components and filters used in these units

quickly becomes clogged with construction dirt and debris

which may cause system damage.

UNIT

50VSA,B

50VSC,D

50VSE,F

50VSG,H

50VSI,J

50VSK,L

50VSM,N

COOLING CAPACITY (Btuh)

9,200

11,700

16,500

18,000

22,500

28,500

32,700

HEATING CAPACITY (Btuh)

12,500

16,000

22,500

24,500

31,000

38,000

45,000

CABINET WEIGHT (lb)

120

170

CHASSIS WEIGHT (lb)

99

105

119

122

187

198

205

COMPRESSOR (1 each)

Rotary

Scroll

High Side Pressure (psig)

550

Low Side Pressure (psig)

170

FACTORY REFRIGERANT CHARGE R-410A (oz)

27.5

27.5

36.7

41.6

49.4

63.5

61.8

FAN DATA

Fan Motor Type/Speeds

PSC/2 speed

Blower Wheel Size (Depth x Width) (in.)

Std/High Static

7.08 x 6.69

9.21 x 9.99

Airflow (cfm)

370

450

540

640

820

1120

1300

Static Pressure (in. wg)

0

WATER/CONDENSATE SIDE DATA

Flow Rate (gpm)

2.6

3.2

4.5

5.2

6.5

8.5

9.5

Water Connection Size (FPT) (in.)

1/2

3/4

Water Side Pressure Drop (psi)

5.8

5.8

11.5

11.8

4.8

7.2

10.2

Condensate Connection Size (in.)

3/4

AIR COIL DATA

Total Face Area (sq ft)

1.48

1.48

1.81

1.48

1.48

1.81

1.48

Tube Size (in.)

3/8

Fin Spacing (FPI)

12

14

10

Number of Rows

2

3

2

3

CABINET DATA

Depth (in.)

18

24

Height (in.)

88

88

Width (in.)

18

24

Standard Filter -- 1 in. Washable

14-1/4 x 18-1/2

14-1/4 x 22-1/2

19 x 28-3/4

FPI

Fins Per Inch

PSC

Permanent Split Capacitor