Oa ) + (tr, Ra ) =t, 50h e, h j – Carrier 50HE003-006 User Manual

Page 40

Advertising
background image

40

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.

deg. F (deg. C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

1

4

1

6

18

20

2

2

24

26

28

30

32

3

4

36

38

40

42

44

46

9

0

1

0

0

80

70

6

0

50

40

30

20

10

ENTHALPY BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

A

A

B

B

C

C

D

D

RELATIVE HUMIDITY (%)

HIGH LIMIT

CURVE

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

C06037

Fig. 43

--- Enthalpy Changeover Set Points

Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled

ventilation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and cool

capacity of the equipment, the maximum ventilation rate must be
evaluated for design conditions. The maximum damper position

must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal

outside air design criteria.
A proportional anticipatory strategy should be taken with the

following conditions: a zone with a large area, varied occupancy,

and equipment that cannot exceed the required ventilation rate at
design conditions. Exceeding the required ventilation rate means

the equipment can condition air at a maximum ventilation rate
that is greater than the required ventilation rate for maximum

occupancy. A proportional-anticipatory strategy will cause the
fresh air supplied to increase as the room CO

2

level increases

even though the CO

2

set point has not been reached. By the time

the CO

2

level reaches the set point, the damper will be at

maximum ventilation and should maintain the set point.
In order to have the CO

2

sensor control the economizer damper in

this manner, first determine the damper voltage output for

minimum or base ventilation. Base ventilation is the ventilation

required to remove contaminants during unoccupied periods. The
following equation may be used to determine the percent of

outside-air entering the building for a given damper position. For
best results there should be at least a 10 degree difference in

outside and return-air temperatures.

(T

O x

OA

) + (TR

x

RA

) =T

M

100

100

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

= Return-Air Temperature

RA = Percent of Return Air

T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the minimum

damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or

maximum ventilation rate to the building. For example, an output

of 3.6 volts to the actuator provides a base ventilation rate of 5%
and an output of 6.7 volts provides the maximum ventilation rate

of 20% (or base plus 15 cfm per person). Use Fig. 42 to
determine the maximum setting of the CO

2

sensor. For example,

a 1100 ppm set point relates to a 15 cfm per person design. Use

the 1100 ppm curve on Fig. 45 to find the point when the CO

2

sensor output will be 6.7 volts. Line up the point on the graph

with the left side of the chart to determine that the range
configuration for the CO

2

sensor should be 1800 ppm. The

EconoMi$er IV controller will output the 6.7 volts from the CO

2

sensor to the actuator when the CO

2

concentration in the space is

at 1100 ppm. The DCV set point may be left at 2 volts since the

CO

2

sensor voltage will be ignored by the EconoMi$er IV

controller until it rises above the 3.6 volt setting of the minimum

position potentiometer.
Once the fully occupied damper position has been determined, set

the maximum damper demand control ventilation potentiometer

to this position. Do not set to the maximum position as this can
result in over-ventilation to the space and potential high-humidity

levels.

50H

E,

H

J

Advertising