Chapter 1. Introduction

DeviceMaster UP Modbus/TCP User Guide: 2000447 Rev. I

Dual Master (Virtual Peer-to-Peer) - Write Mode

1.4.4.3. Dual Master (Virtual Peer-to-Peer) - Write Mode

Dual master (virtual peer-to-
peer) - write
mode:

•

The DeviceMaster UP
and PLC initiate only
write messages to each
other.

•

The DeviceMaster UP
writes received serial
and/or Ethernet device
data directly into PLC
memory with minimal
latency.

•

The PLC can write to
serial and/or Ethernet devices through the DeviceMaster UP with minimal latency.

•

This mode provides the lowest possible Ethernet bandwidth usage and most efficient usage of PLC and
DeviceMaster UP processing power.

•

Only raw/ASCII devices are supported in this mode.

•

The DeviceMaster UP Receive Transfer mode is set to Master and Transmit Transfer mode is set to Slave.

1.4.4.4. Dual Master (Virtual Peer-to-Peer) - Read Mode (Dual Polling)

Dual master (virtual peer-to-
peer) - read mode (dual
polling)
:

•

This is provided for
programmers who
strongly prefer polling.

•

The DeviceMaster UP
and PLC initiate only
read messages to each
other.

•

The PLC will poll for
received serial and/or
Ethernet device data.

•

The DeviceMaster UP polls for transmit data to serial and/or Ethernet devices.

•

This mode requires the highest possible Ethernet bandwidth usage and provides the least efficient usage
of PLC and DeviceMaster UP processing power.

•

Only raw/ASCII devices are supported in this mode.

•

The DeviceMaster UP Receive Transfer mode is set to Slave and Transmit Transfer mode is set to Master.