DeviceMaster UP Modbus/TCP User Guide: 2000447 Rev. I

Chapter 2. Programming Interface - 19

What is Modbus/TCP?

2.1.4. What is Modbus/TCP?

Modbus/TCP is an Ethernet network based protocol that contains a Modbus/RTU message, with the exception
of the 2 byte CRC. The Modbus/TCP message contains a header with information designed to provide message
identification and routing information. The format is as follows:

Where:

•

The terms Master or Client are used to identify the sender of the message.

•

The terms Slave or Server are used to identify the devices responding to the message.

•

Modbus TCP messages are typically sent to and received on a defined Ethernet TCP/IP socket of 502.

•

Modbus TCP implementations provide more capability, but also require more processing than simpler
Modbus/RTU implementations.

Modbus TCP is used for connecting advanced Ethernet based devices, such as PLCs, HMIs, SCADA Systems,
and most OPC Servers to:

•

Other Ethernet devices supporting Modbus TCP.

•

Serial Modbus/RTU and/or Modbus/ASCII devices through gateways (such as the DeviceMaster UP
running the Modbus/TCP or Modbus Router applications).

•

Serial or Ethernet TCP/IP raw/ASCII devices (barcode scanners, printers, RFID readers, visions systems,
etc) through a gateway (such as the DeviceMaster UP running the Modbus/TCP application).

2.2. Raw Data Interface

This subsection contains the following topics:

•

Supported Modbus Messages

on Page 19

•

Serial Port Raw/ASCII Interface

on Page 20

•

Ethernet Device Raw/ASCII Interface

on Page 21

•

Receive Data Message (Raw Data)

on Page 23

•

Transmit Data Message (Raw Data)

on Page 25

•

Sequence Number Messages (Raw Data)

on Page 27

2.2.1. Supported Modbus Messages

DeviceMaster UP supports the following Modbus messages over Modbus/TCP for raw data transfer.

Note: Your PLC programming software may not allow maximum size serial packets.

Message Type

Function Code

Maximum Message Size

Maximum Serial Packet Size

Read Holding Registers 3

250 BYTEs (125 WORDs)

246 BYTEs (123 WORDs)

Write Multiple Registers 16 (10 hex)

240 BYTEs (120 WORDs)

236 BYTEs (118 WORDs)

Read/Write Multiple
Registers

23 (17 hex)

236 BYTEs (118 WORDs)

232 BYTEs (116 WORDs)