IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A

Chapter 2. Functionality Descriptions - 17

Chapter 2. Functionality Descriptions

This appendix discusses the following:

•

2.1. Event Handling

•

2.2. ISDU Handling

on Page 21

2.1. Event Handling

The IO-Link Master event handling is designed to provide real-time updates of event codes received directly
from the IO-Link device. The IO-Link event code:

•

Is included in the second 16-bit word of the Input Process Data (PDI) block.

-

An active event is indicated by a non-zero value.

-

Inactive or no event is indicated by a zero value.

•

Two methods are provided to clear an event:

-

Enable the Clear Event After Hold Time option.

•

The IO-Link Master keeps, or holds, the active event code in the PDI block until the configured Active
Event Hold Time
has passed.

•

The IO-Link Master then clears the event code in the PDI block and waits until the Clear Event Hold
Time
has passed before including another event code in the PDI block.

-

Enable the Clear Event In PDO Block option.

• The IO-Link Master monitors the PDO block received from the PLC.

• The IO-Link Master expects the first entry of the PDO block to indicate an event code to be cleared.

• If there is an active event code in the PDI block and the PDO block both contain the same event

code, the event code is cleared in the PDI block.

• The IO-Link Master then clears event code in the PDI block and waits until the Clear Event Hold

Time has passed before including another event code in the PDI block.

•

The two methods can be used separately or together to control clearing of events.

The next subsections illustrate the event clearing process for the various event configurations.