Table 7 — electrical data, 074 units (cont) – Carrier NP034-074 User Manual

Page 33

Advertising
background image

Table 7 — Electrical Data, 074 Units (cont)

575-3-60 (V-Ph-Hz)

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

BASE UNIT

ONLY

EXHAUST

FAN

ELECTRIC

HEAT*

BASE UNIT WITH

EXHAUST FAN

AND/OR

ELECTRIC HEAT*

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

MCA

MOCP

Total

Hp

Total

FLA

kW

FLA

MCA

MOCP

518-632

39.1

176.0

52.6

276.0

12.0

15.0

17.0

133.8

175

10.0

12.2

—

—

146.0

175

15.0

18.0

—

—

151.8

200

20.0

22.0

—

—

155.8

200

—

—

36

36.0

133.8

175

—

—

72

72.0

133.8

175

—

—

108†

108.0

156.2

175

10.0

12.2

36

36.0

146.0

175

10.0

12.2

72

72.0

146.0

175

10.0

12.2

108†

108.0

156.2

175

15.0

18.0

36

36.0

151.8

200

15.0

18.0

72

72.0

151.8

200

15.0

18.0

108†

108.0

156.2

200

20.0

22.0

36

36.0

155.8

200

20.0

22.0

72

72.0

155.8

200

20.0

22.0

108†

108.0

156.2

200

20.0

22.0

138.8

175

10.0

12.2

—

—

151.0

200

15.0

18.0

—

—

156.8

200

20.0

22.0

—

—

160.8

200

—

—

36

36.0

138.8

175

—

—

72

72.0

138.8

175

—

—

108†

108.0

162.5

175

10.0

12.2

36

36.0

151.0

200

10.0

12.2

72

72.0

151.0

200

10.0

12.2

108†

108.0

162.5

200

15.0

18.0

36

36.0

156.8

200

15.0

18.0

72

72.0

156.8

200

15.0

18.0

108†

108.0

162.5

200

20.0

22.0

36

36.0

160.8

200

20.0

22.0

72

72.0

160.8

200

20.0

22.0

108†

108.0

162.5

200

25.0

27.0

143.8

175

10.0

12.2

—

—

156.0

200

15.0

18.0

—

—

161.8

200

20.0

22.0

—

—

165.8

200

—

—

36

36.0

143.8

175

—

—

72

72.0

143.8

175

—

—

108†

108.0

168.7

200

10.0

12.2

36

36.0

156.0

200

10.0

12.2

72

72.0

156.0

200

10.0

12.2

108†

108.0

168.7

200

15.0

18.0

36

36.0

161.8

200

15.0

18.0

72

72.0

161.8

200

15.0

18.0

108†

108.0

168.7

200

20.0

22.0

36

36.0

165.8

200

20.0

22.0

72

72.0

165.8

200

20.0

22.0

108†

108.0

168.7

200

30.0

32.0

148.8

200

10.0

12.2

—

—

161.0

200

15.0

18.0

—

—

166.8

200

20.0

22.0

—

—

170.8

200

—

—

36

36.0

148.8

200

—

—

72

72.0

148.8

200

—

—

108†

108.0

175.0

225

10.0

12.2

36

36.0

161.0

200

10.0

12.2

72

72.0

161.0

200

10.0

12.2

108†

108.0

175.0

225

15.0

18.0

36

36.0

166.8

200

15.0

18.0

72

72.0

166.8

200

15.0

18.0

108†

108.0

175.0

225

20.0

22.0

36

36.0

170.8

200

20.0

22.0

72

72.0

170.8

200

20.0

22.0

108†

108.0

175.0

225

LEGEND

CV

— Constant Volume

ETL

— ETL Testing Laboratory

FLA

— Full Load Amps

Hp

— Nominal Horsepower

IFM

— Indoor (Evaporator) Fan Motor

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
OFM

— Outdoor (Condenser) Fan Motor

RLA

— Rated Load Amps

*Electric heat available on 50 Series vertical discharge units.

†108 kW available on CV applications only.

NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To de-

termine heater capacity (kW) at unit operating voltage, multiply 240 v, 480
v, or 575 v capacity by appropriate multiplier below.

MULTIPLICATION FACTORS

HEATER kW

RATING

VOLTAGE

DISTRIBUTION

V-3-60

MULTIPLICATION

FACTOR

240

200
208
230
240

0.694
0.751
0.918
1.000

480

440
460
480

0.840
0.918
1.000

575

550
575
600

0.915
1.000
1.089

Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.

2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series

units only.

33