Premier series monitor, Operation, Alarm – Eagle Microsystems GD-1000 User Manual

Page 3

Advertising
background image

EAGLE MICROSYSTEMS. INC.
Instrumentation for Measurement and Control

3

copyright 2/02

Premier Series Monitor

OPERATION:

MAIN RUN SCREEN:

The value displayed is the type of sensor and its scaled output in ppm.
Below the sensor type and value is a fifty segment bar-graph representation
of the monitors full scale and the 4mA to 20mA output (PO1). To enter the
configuration and calibration screens press SET. The display will prompt
you to enter a password.

1
2
3

4

SET

Press SET to enter a password screen.

PASSWORD ENTRY SCREEN:

From the run screen, press SET and the user will be prompted to enter a
password (default is 000). If the password is correct, the MONITOR SETUP
SCREEN will be displayed. If an incorrect password is entered, The MAIN
RUN SCREEN will be displayed.

1

?, 0-9

Steps from 0 to 9 and then back to 0.

2

?, 0-9

Steps from 0 to 9 and then back to 0.

3

?, 0-9

Steps from 0 to 9 and then back to 0.

4

ENT

Press ENT to enter monitor setup screen..

MONITOR SETUP SCREEN:

From the Monitor Setup screen, you can select CAL, ALM or RUN. The
Calibration screen provides the ability to calibrate the analog input and
output. The alarm screen provides the ability to set the Danger and Critical
values.

1

CAL

Enter calibration screen.

2

ALM

Enter danger and critical alarm setup screen

3
4

RUN

Go back to the main run screen.

Premier Series Monitor

ALARM:

SELECT ALARM:

From the MONITOR SETUP SCREEN, press the pushbutton under ALM.

1

CAL

Enter calibration screen

2

ALM

Enter alarm select screen

3
4

RUN

Go back to the main run screen

SO2

0.0 ppm

IIIIIIIIIIIIIIIIIIIIIIIIII

SET

ENTER PASSWORD

?

?

?

ENT

MONITOR SETUP
CAL

ALM

RUN

MONITOR SETUP
CAL

ALM

RUN