EVCO EVRS235N9 User Manual
Page 3

EVCO S.p.A. | Code 104RS235E104 | Page 3 of 10 | PT 07/14 | version 1.0
To select an alarm:
5.
Press and release the
key or the
key.
To see information regarding the alarm:
6.
Press and release the
key: the HACCP LED will stop
flashing and remain on permanently and the display will
show, for example, the following information in succes-
sion:
Inform. Part
8.0
the critical value is 8.0 °C/8 °F
StA
the display is about to show the date and time at
which the alarm occurs (EVRS235 model only)
y14
the alarm occurred in 2014 (continue...)
n03
the alarm occurred in the month of March (conti-
nue...)
d26
the alarm occurred on 26 March 2014 (continue...)
h16
the alarm occurred at 16:00 (continue...)
n30
the alarm occurred at 16:30
dur
the display is about to show the alarm duration
h01
the alarm lasted for 1 hour (other data continues)
n15
the alarm lasted 1 hour and 15 min
code the alarm selected
the displays each piece of information for 1 s.
To exit the information sequence:
7.
Press and release the
key: the display will show
the alarm selected.
To exit the procedure:
8.
Exit the information sequence.
9.1 Press and release the
or
key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
9.2 Press and release the
key.
6.3
Cancelling the HACCP alarm list
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the
key down for 1 s: the display will show the
first label available.
3.
Press and release the
key or
the key to select
“rLS”.
4.
Press and release the
key.
5.
Press and release the
key or the
key within
15 s to set “149”.
6.
Press and release the
key or do not operate for
15 sec: the display will show a flashing “- - - -” for
4 sec and the “HACCP” LED switches off, after which
the device will exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
7
COMPRESSOR OPERATING HOURS COUNT
7.1
Preliminary notes
The device can memorise up to 999 comp. operating hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for mainte-
nance is signalled.
7.2
Display of Compressor Operation Hours
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the
key down for 1 s: the display will show the
first label available.
3.
Press and release the
key or the
key to select
“CH”.
4.
Press and release the
key.
To exit the procedure:
5.
Press and release the
key or do not operate for
60 sec.
6.1 Press and release the
or
key until the display
shows the magnitude established with parameter P5 or
do not operate for 60 sec.
Alternatively:
6.2 Press and release the
key.
7.3
Cancelling the HACCP alarm list
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the
key down for 1 s: the display will show the
first label available.
3.
Press and release the
key or the
key to select
“rCH”.
4.
Press and release the
key.
5.
Press and release the
key or the
key within
15 s to set “149”.
6.
Press and release the
key or do not operate for
15 sec: the display will show “- - -” flashing for
4 sec, after which the device will exit the procedure.
8
SYNCHRONISATION OF DEFROSTING PERI-
ODS (ONLY IF PARAMETER i0 IS SET AT 6)
8.1
Preliminary notes
The activation of defrosting causes the activation of the
digital input (at maximum for the time established with
parameter d24 or until the conclusion of predripping).
If the digital input is connected in parallel to the digital input of
other devices configured in the same way, the activation of the
input caused the activation of defrosting in the other devices.
The devices start dripping simultaneously with the conclu-
sion of the predripping of the last device to end the same.
9
SETTINGS
9.1
Setting the date, time and day of the week
(EVRS235 model only)
The date can be set in the day-month-year format; the
time in the hours-minutes format (24 h).
To access the procedure:
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Hold the
key down for 1 s: the display will show the
first label available.
3.
Press and release the
key or the
key to select
“rtc”.
To set the year:
4.
Press and release the
key: the display will show
“y” followed by the last two numbers of the year.
5.
Press and release the
key or the
key within
15 sec.
To set the month:
6.
Press and release the
key when setting the year:
the display will show “n” followed by the number of the
month
7.
Press and release the
key or the
key within
15 sec.
To set the day:
8.
Press and release the
key when setting the month:
the display will show “d” followed by the number of the
day.
9.
Press and release the
key or the
key within
15 sec.
To set the hour:
10. Press and release the
key when setting the day:
the display will show “h” followed by the number of the
hour.
11. Press and release the
key or the
key within
15 sec.
To set the minute:
12. Press and release the
key when setting the hour:
the display will show “n” followed by the number of the
minute.
13. Press and release the
key or the
key within
15 sec.
To set the day of the week:
14. Press and release the
key when setting the minute:
the display will show the first label available.
15. Press and release the
key or the
key within
15 sec to set:
-
“Mon” (Monday)
-
“tuE” (Tuesday)
-
“UEd” (Wednesday)
-
“thu” (Thursday)
-
“Fri” (Friday)
-
“SAt” (Saturday)
-
“Sun” (Sunday).
16. Press and release the
key: the device will exit the
procedure.
To exit the procedure before the operation is complete:
17. Do not operate for 60 sec (any changes will be saved).
9.2
Setting the working set point
1.
Make sure that the keyboard is not locked and that no
procedure is in progress.
2.
Press and release the
key: the LED will flash.
3.
Press and release the
or
key within
15 sec; see also parameters r1, r2 and r3
4.
Press and release the
key or do not operate for
15 sec: the LED will switch off after which:
-
if the parameter F0 is set at 0, 1, 2, 3 or 4, the device
will exit the procedure
-
if parameter F0 is set at 5, the device will access the
procedure to set the evaporator fan speed; see para-
graph 9.3
To exit the procedure before the operation is complete:
5.
Do not operate for 15 sec (any changes will be saved).
The working set point can also be set via parameter SP.
9.3
Setting evaporator fan speed (intended as
percentage of max. speed and in case of ana-
logue management)
1.
Press and release the
key while setting the work
set point: the
LED will flash.
2.
Press and release the
or
key within
15 sec; see also parameters F15 and F16.
3.
Press and release the
key or do not operate for
15 sec: the LED will switch off and then the device
will exit the procedure.
To exit the procedure before the operation is complete:
5.
Do not operate for 15 sec (any changes will be saved).
The evaporator fan speed can also be set through parameter F17.
9.4
Setting the configuration parameters
To begin the procedure:
1.
Make sure no procedures are in progress
2.
Hold the
key and the
key down for 4 s:
the display will show “PA”.
3.
Press and release the
key.
4.
Press and release the
key or the
key within
15 s to set “-19”.
5.
Press and release the
key or do not operate for
15 sec.
6.
Hold the
key and the
key down for 4 s:
the display will show “SP”.
To select a parameter:
7.
Press and release the
key or the
key.
To set a parameter:
8.
Press and release the
key.
9.
Press and release the
key or the
key within
15 sec.
10. Press and release the
key or do not operate for
15 sec.
To exit the procedure:
11. Hold down the
and
keys for 4 sec and do not
operate for 60 sec (any changes will be saved).
After setting the parameters, suspend power supply flow to
the device.
9.5
Restoring the Manufacturer’s Settings
To begin the procedure:
1.
Make sure no procedures are in progress
2.
Hold the
key and the
key down for 4 s:
the display will show “PA”.
3.
Press and release the
key.
4.
Press and release the
key or the
key within
15 s to set “149”.
5.
Press and release the
key or do not operate for
15 sec.
6.
Hold the
key and the
key down for 4 s:
the display will show “dEF”.
7.
Press and release the
key.
8.
Press and release the
key or the
key within
15 s to set “1”.
9.
Press and release the
key or do not operate for
15 sec: the display will show “dEF” flashing for
4 sec, after which the device will exit the procedure.
10. Cut the device power supply off.
To exit the procedure in advance:
11. Hold the and key down for 4 s during the procedure
(i.e. before setting “1”: Restore will not be performed).
Make sure that the manufacturer’s settings are appropriate
(see chapter 14).
10
WARNING LIGHTS AND DIRECTIONS
10.1
Signals
LED
Part
compressor LED light
if the LED is on, then the compressor is on
if the LED is flashing:
-
the working set point is in the process of being
set (via the procedure described in paragraph
9.2)
-
a compressor protection will be in progress;
see parameters C0, C1, C2, C14, C15, C16
and i7
Defrost LED
If it is on:
-
defrosting is in progress
-
predripping will be in progress; see parameter
d16
if the LED is flashing:
-
defrosting will be requested but a compressor
protection will be in progress; see the param-
eters C0, C1 and C2
-
dripping will be in progress; see parameter d7
-
the refrigerant fluid heating will be in progress;
see parameter d15
Evaporator fan LED light
If it is on:
-
setting the evaporator fan speed will be in
progress (via the procedure explained in para-
graph 9.3)
-
the evaporator fan will be on
if the LED is flashing:
-
evaporator fan standstill will be in progress;
see parameter F3
AUX auxiliary LED
If it is on:
-
the cabinet light will have been switched on in
manual mode (only if parameter u1 and/or
parameter u11 is set at 0)
-
the demister heating elements will be switched
on (only if the parameter u1 and/or param-
eter u11 is set at 1)