EVCO EVRS235N9 User Manual

Page 6

Advertising
background image

EVCO S.p.A. | Code 104RS235E104 | Page 6 of 10 | PT 07/14 | version 1.0

14

WORKING SETPOINT AND CONFIGURATION PARAMETERS

14.1

Working set-point

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 WORKING SETPOINT

r1

r2

°C/°F (1) -18,0

-18,0

working set-point; see also r0

14.2

Configuration parameters

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 WORKING SETPOINT

SP

r1

r2

°C/°F (1) -18,0

-18,0

working set-point; see also r0

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 MEASUREMENT INPUTS

CA1

-25

25,0 °C/°F (1)

0,0

0,0

if P4 = 0, 1 or 2, cabinet probe offset
if P4 = 3, inlet air probe offset

CA2

-25

25,0 °C/°F (1)

0,0

0,0

offset evaporator probe

CA3

-25

25,0 °C/°F (1)

0,0

0,0

if P4 = 1, condenser probe offset
if P4 = 2, display probe offset
if P4 = 3,outlet air probe offset

P0

0

2

- - -

1

1

probe type
0

=

PTC

1

=

NTC

2

=

Pt 1000

P1

0

1

- - -

1

1

degree Celsius decimal point (during normal operation)
1

=

YES

P2

0

1

- - -

0

0

temperature unit of measurement (2)
0

=

°C

1

=

°F

P3

0

2

- - -

1

1

evaporator probe function
0

=

probe absent

1

=

defrosting probe and probe for evaporator fan thermostating

2

=

probe for evaporator fan thermosatating

P4

0

3

- - -

3

3

third input function
0

=

digital input (micro switch/multi-function input 1)

1

=

analogue input (condenser probe)

2

=

analogue input (display probe)

3

=

analogue input (output air probe)

P5

0

4

- - -

0

0

magnitude displayed during normal operation
0

=

if P4 = 0, 1 or 2, cabinet temperature
if P4 = 3, CPT temperature

1

=

work set-point

2

=

evaporator temperature

3

=

if P4 = 1, condenser temperature
if P4 = 2, temperature detected by the display probe
if P4 = 3, temperature detected by the outlet air probe

4

=

if P4 = 3, temperature detected by the inlet air probe

P6

0

5

- - -

5

5

magnitude displayed by the remote indicator
0

=

if P4 = 0, 1 or 2, cabinet temperature
if P4 = 3, CPT temperature

1

=

work set-point

2

=

evaporator temperature

3

=

if P4 = 1, condenser temperature
if P4 = 2, temperature detected by the display probe
if P4 = 3, temperature detected by the outlet air probe

4

=

if P4 = 3, temperature detected by the inlet air probe

5

=

the remote indicator will not be enabled

P7

0

100

%

50

50

percentage of the temperature detected by the inlet air probe for the calculation of the CPT temperature (only if P4=3)

P8

0

250

0.1 s

5

5

delay displaying temperature variation detected by the probes

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 MAIN REGULATOR

r0

0,1 (3)

15,0 °C/°F (1)

2,0

2,0

working set-point differential

r1

-99

r2

°C/°F (1)

-50

-50

minimum working set-point

r2

r1

99,0 °C/°F (1) 50,0

50,0

maximum working set-point

r3

0

1

- - -

0

0

locking of working set-point setting (using the procedure described in paragraph 9.2)
1

=

YES

r4

0,0

99,0 °C/°F (1)

0,0

0,0

increase in temperature during “energy saving” function; see also i0, i5, i10, H01... H14

r5

0,0

99,0 °C/°F (1)

0,0

0,0

decrease in temperature during “overcooling” function; see also r6

r6

0

240

min

30

30

duration of “overcooling” function; see also r5

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 COMPRESSROR PROTECTION SYSTEM

C0

0

240

min

0

0

delay in switching on of compressor after the device switches on (4)

C1

0

240

min

5

5

minimum time between two consecutive compressor start-ups; also delay in compressor start-up after conclusion of cell probe error
(code “Pr1”) (5) (6)

C2

0

240

min

3

3

minimum compressor switch-off duration; see also C18 (5) (7)

C3

0

240

s

0

0

minimum duration of compressor switch on time

C4

0

240

min

10

10

duration of compressor switch off during cabinet probe/inlet air probe error (code “Pr1”); see also C5

C5

0

240

min

10

10

duration of compressor switch on during cabinet probe/inlet air probe error (code “Pr1”); see also C4

C6

0,0

199

°C/°F (1) 80,0

80,0

condenser temperature is higher than that at which the condenser overheating alarm is activated (code “COH”) (8)

C7

0,0

199

°C/°F (1) 90,0

90,0

condenser temperature above which the blocked compressor alarm is activated (“CSd” code)

C8

0

15

min

1

1

blocked compressor alarm delay (“CSd” code) (9)

C10

0

999

10 h

0

0

number of operating hours is higher than the limit at which the need for maintenance is signalled.
0

=

function absent

C11

0

240

s

3

3

compressor 2 switch-on delay from compressor 1 switch-on (only if u1 and/or u11 = 7) (10)

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 DEFROSTING

d0

0

99

h

8

8

if d8 = 0, 1 or 2, defrosting interval (11)
0

=

interval defrosting will never be activated

if d8 = 3, maximum defrost interval

d1

0

2

- - -

0

0

type of defrosting
0

=

ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; evaporator fan
activity will depend on parameter F2

1

=

BY HOT GAS - during defrosting the compressor will be switched on and the defrosting output will be activated; evaporator
fan activity will depend on parameter F2

2

=

VIA STOPPING OF COMPRESSOR - during defrosting the compressor will remain switched off and the defrosting output will
remain deactivated; evaporator fan activity will depend on parameter F2

d2

-99

99,0 °C/°F (1)

2,0

2,0

temperature at end of defrosting (only if P3 = 1); see also d3

d3

0

99

min

30

30

se P3 = 0 or 2, defrosting duration
se P3 = 1, maximum defrosting duration; see also d2
0

=

defrosting will not be activated

Advertising
This manual is related to the following products: