EVCO EVRS235N9 User Manual

Page 9

Advertising
background image

EVCO S.p.A. | Code 104RS235E104 | Page 9 of 10 | PT 07/14 | version 1.0

i10

0

999

min

0

0

time that must pass in absence of door micro switch input activations (after the cabinet temperature or the CPT temperature has
reached the work set point) for the “energy saving” function to be activated; see also r4, H01... H14
0

=

the function will never be activated due to the effect of this condition

i13

0

240

- - -

180

180

number of door switch input activations such as to provoke the defrost activation
0

=

defrosting will never be activated due to the effect of this condition

i14

0

240

min

32

32

minimum duration of the door switch input activation such as to provoke the defrost activation
0

=

defrosting for this condition will never be activated

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 DIGITAL OUTPUTS

u1

0

7

- - -

0

0

operation controlled by fourth output (32)
0

=

CABINET LIGHT - in this case the key and parameters i0, i5 AND u2 will be activated

1

=

DEMISTER HEATING ELEMENTS - in this case the key and parameter u6 will be activated

2

=

AUXILIARY OUTPUT - in this case the key and parameters i5 and u2 will be activated

3

=

ALARM OUTPUTS - in this case parameter u4 will be activated

4

=

DOOR HEATING ELEMENTS - in this case parameter u5 will be activated

5

=

HEATING ELEMENTS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated

6

=

CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated

7

=

COMPRESSOR 2 - in this case, parameter C11 will assume significance of

u2

0

1

- - -

0

0

enabling of manual switch on/switch off of the cabinet light or the auxiliary output when the device is switched off(only if u1 and/
or u11= 0 or 2) (33)
1

=

YES

u4

0

1

- - -

1

1

enabling of alarm output deactivation with the silencing of the buzzer (only if u1 and/or u11 = 3)
1

=

YES

u5

-99

99,0 °C/°F (1)

-1,0

-1,0

temperature of the cabinet or CPT temperature below which the door heating elements are switched on (“u5 - 2,0 °C/4 °F, only if
u1 and/or u11 = 4) (8)

u6

1

120

min

5

5

operating time of demister heating elements (only if u1 and/or u11 = 1)

u7

-99

99,0 °C/°F (1)

-5,0

-5,0

neutral area value (relative to the work set-point, i.e. “work set-point + u7) (only if u1 and/or u11 = 5) (34)

u8

- - -

- - -

- - -

- - -

- - -

reserved

u9

0

1

- - -

1

1

enabling the buzzer
1

=

YES

u11

0

7

- - -

3

3

operation controlled by fifth output (32)
0

=

CABINET LIGHT - in this case the key and parameters i0 and u2 will be activated

1

=

DEMISTER HEATING ELEMENTS - in this case the key and parameter u6 will be activated

2

=

AUXILIARY OUTPUT - in this case the key and parameters i0 and u2 will be activated

3

=

ALARM OUTPUTS - in this case parameter u4 will be activated

4

=

DOOR HEATING ELEMENTS - in this case parameter u5 will be activated

5

=

HEATING ELEMENTS FOR NEUTRAL AREA OPERATION - in this case parameter u7 will be activated

6

=

CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated

7

=

COMPRESSOR 2 - in this case, parameter C11 will assume significance of

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 ENERGY SAVING

HE2

0

999

min

0

0

maximum duration of the “energy saving” function activated due to the effect of absence of door micro switch input activation
0

=

the function will last until the input is activated

H01

0

23

h

not avail.

0

activation time of the “energy saving” function every Monday; see also r4, F13, F14 and H02

H02

0

24

h

not avail.

0

duration of the “energy saving” function every Monday; see also H01

H03

0

23

h

not avail.

0

activation time of the “energy saving” function every Tuesday; see also r4, F13, F14 and H04

H04

0

24

h

not avail.

0

duration of the “energy saving” function every Tuesday; see also H03

H05

0

23

h

not avail.

0

activation time of the “energy saving” function every Wednesday; see also r4, F13, F14 and H06

H06

0

24

h

not avail.

0

duration of the “energy saving” function every Wednesday; see also H05

H07

0

23

h

not avail.

0

activation time of the “energy saving” function every Thursday; see also r4, F13, F14 and H08

H08

0

24

h

not avail.

0

duration of the “energy saving” function every Thursday; see also H07

H09

0

23

h

not avail.

0

activation time of the “energy saving” function every Friday; see also r4, F13, F14 and H10

H10

0

24

h

not avail.

0

duration of the “energy saving” function every Friday; see also H09

H11

0

23

h

not avail.

0

activation time of the “energy saving” function every Saturday; see also r4, F13, F14 and H12

H12

0

24

h

not avail.

0

duration of the “energy saving” function every Saturday; see also H11

H13

0

23

h

not avail.

0

activation time of the “energy saving” function every Sunday; see also r4, F13, F14 and H14

H14

0

24

h

not avail.

0

duration of the “energy saving” function every Sunday; see also H13

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 DEFROSTING IN REAL TIME

Hd1

h0

h - -

h

not avail. h - -

time of activation of first daily defrosting (only if d8 = 4)
h - -=

the first defrosting will not be activated

Hd2

h0

h - -

h

not avail. h - -

time of activation of second daily defrosting (only if d8 = 4)
h - -=

the second defrosting will not be activated

Hd3

h0

h - -

h

not avail. h - -

time of activation of third daily defrosting (only if d8 = 4)
h - -=

the third defrosting will not be activated

Hd4

h0

h - -

h

not avail. h - -

time of activation of fourth daily defrosting (only if d8 = 4)
h - -=

the fourth defrosting will not be activated

Hd5

h0

h - -

h

not avail. h - -

time of activation of fifth daily defrosting (only if d8 = 4)
h - -=

the fifth defrosting will not be activated

Hd6

h0

h - -

h

not avail. h - -

time of activation of sixth daily defrosting (only if d8 = 4)
h - -=

the sixth defrosting will not be activated

PARAM.

MIN.

MAX.

U.M.

EVRS225 EVRS235 SERIAL NETWORK

LA

1

247

- - -

247

247

device address

Lb

0

3

- - -

2

2

baud rate
0

=

2.400 baud

1

=

4.800 baud

2

=

9.600 baud

3

=

19.200 baud

LP

0

2

- - -

2

2

parity
0

=

none (no parity)

1

=

odd

2

=

even

Notes:
(1)

the unit of measurement depends on P2

(2)

Properly set the parameters corresponding to the regulators after setting parameter P2

(3)

the value depends on parameter P2 (0.1 °C or 1 °F)

(4)

the parameter has effect even after an interruption in the power supply that occurs while the device is switched on

(5)

the time established with the parameter is counted even when the device is switched off

(6)

if parameter C1 is set at 0, the delay after the end of the cabinet probe error will be 2 min

(7)

if parameter C2 is set at 0, the device will function as if parameter C18 were set at 0

(8)

The parameter differential is 2.0 °C/4 °F

(9)

if when the device is switched on, the condenser temperature is already above that established in parameter C7, then parameter C8 will not have effect

(10)

compressor 2 is switched off when compressor 1 is switched off