Deg c) – Carrier AQUAZONE 50VQP084-300 User Manual

Page 48

Advertising
background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500080-01

Printed in U.S.A.

Form 50VQP-C1SI

Pg CL-2

11-10

Replaces: New

Copyright 2010 Carrier Corporation

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

- -

-

- -

-

- -

-

- -

-

- -

- -

-

--

- -

-

- -

- -

-

- -

-

- -

-

- -

- - -

CUT

AL

ONG DO

TT

E

D

LINE

CU

T ALONG DO

TT

E

D

LINE

HEATING CYCLE ANALYSIS

COOLING CYCLE ANALYSIS

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (L/s) x

TEMP. DIFF. (DEG. C) x

FLUID FACTOR* =

(kW)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=

(DEG C)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=

(DEG C)

*Use 500 for water, 485 for antifreeze.

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

°C

°C

AIR

COIL

°C

kPa

WATER OUT

WATER IN

°C

kPa

LOOK UP PRESSURE DROP IN TABLE 8
TO DETERMINE FLOW RATE

°C

LIQUID LINE

kPa

°C

DEW
POINT

LOOK UP PRESSURE DROP IN TABLE 17
TO DETERMINE FLOW RATE

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

°C

°C

AIR

COIL

°C

kPa

WATER OUT

WATER IN

°C

kPa

LOOK UP PRESSURE DROP IN TABLE 8
TO DETERMINE FLOW RATE

°C

LIQUID LINE

kPa

°C

DEW
POINT

LOOK UP PRESSURE DROP IN TABLE 17
TO DETERMINE FLOW RATE

Advertising