Evd120, Programming, 2programming – EVCO EVD120 User Manual

Page 11

Advertising
background image

11

EVD120

Programming

2

Programming

2.1

Preliminary remarks

EVD120 supports the MODBUS communication protocol.

The kind of network EVD120 can work in is RS-485 (look at Fig. 4); for further information on the realization of the

network, consult the Installation manual of RICS for Windows

®

(the document is available in the CD of RICS).

According to the standard settings:

•

the instrument address has value 247

•

the baud rate has value 9,600 baud

•

the parity has value even.

These parameters are hereinafter called “network parameters”.

2.2

Programming an EVD120 having standard network parameters using the soft-
ware RICS (adding an EVD120 having standard network parameters to an
existing and working network of instruments managed by RICS)

Operate as follows:

•

make sure the network is made of instruments that support the MODBUS communication protocol; to learn the

communication protocol supported by the instruments, consult the List of compatible instruments and supported

communication protocol (the document is available in the internet site www.evco.it)

•

make sure the network is made of less than 32 instruments

•

make sure no instrument in the network has value 247 as instrument address; to learn the instrument address,

consult the instructions (the document is available in the internet site www.evco.it)

•

make sure the baud rate of the instruments in the network has value 9,600 baud; to learn the baud rate of the

instrument, consult the instructions (the document is available in the internet site www.evco.it)

•

make sure the parity of the instruments in the network has value even; to learn the parity of the instrument, consult

the instructions (the document is available in the internet site www.evco.it)

•

quit RICS

•

disconnect the power supply of the instruments in the network

•

connect terminal “ + ” of the hardware driver of the last instrument in the network to terminal “ 1 ” of EVD120

(1)

•

connect terminal “ -- ” of the hardware driver of the last instrument in the network to terminal “ 2 ” of EVD120

(1)

•

connect terminal “ S ” of the hardware driver of the last instrument in the network to terminal “ 3 ” of EVD120

(2)

•

to reduce the reflections on the signal transmitted through the cable, plug in the termination of the first and last

element of the network

Fig. 4 - Example of RS-485 network.