FSC verifies proper Airflow

Begins Pilot Trial For Ignition and turns on PTFI LED

The pilot gas solenoid valve is opened, the spark igniter begins sparking, and the flamerod
sensor watches for flame initiation

When flame is established, the FLAME LED is illuminated and main valve opens and the
FSC powers the modulating gas system system and gas flow begins modulating

The FSC monitors the flame while the modulating system adjusts to the selected
temperature

The modulating system checks the discharge air temperature (and the room temperature for the
Maxitrol 44) and regulates the gas going to the burner to satisfy the temperature setting. This system
will modulate the main burner gas from 100% down to 5% as needed.

Optional Remote Panel Circuit

Power

Supply From

Heater

"Power" Light

On

Off

No Power to

Panel

Panel is

Powered

Blower Switch

Nothing Happens

No Power is Sent

to Heater

Power is Sent to

Heater to Open

Damper (if

provided) and

Start Blower

"Off"

Position

(3-Position Panels Only)

"Manual"

"Blower On"

Light

Damper is not

Open or Freeze-

Stat has Detected

Low Temperature

Operation

On

Off

Temperature

Control Switch

Blower Operates

Heat Does not

Operate

"Vent"

Position

"Heat"

Position

Heat Circuit is Energized

"Burner On" Light Illuminates with

proper flame.

"Flame Failure" Light illuminates

if proper flame is not established

Blower Operates

Cooling Circuit is

Energized

"Cool"

Position

(if provided)

Power is Sent to

Heater to Open

Damper (if

provided) and

Start Blower

"Blower On"

Light

Damper is not

Open or Freeze-

Stat has Detected

Low Temperature

Operation

On

Off

Intake Air

Thermstat is

Powered

Intake Air is Cooler Than

Thermostat Set-Point

Nothing Happens

Intake Air is

Warmer Than

Thermostat

Set-Point

"Auto"

Heat Circuit is Energized

"Burner On" Light Illuminates with

proper flame.

"Flame Failure" Light illuminates

if proper flame is not established