To adjust display brightness, To adjust display contrast, Troubleshooting – Interlogix ATP1000 User Manual

Page 4: To change the touchpad unit number, Changing the touchpad unit number

Advertising
background image

To adjust display brightness:

1. Enter user programming mode by pressing 9 + user,

partition, or system master CODE. The display shows

SYSTEM MENU, then TIME AND DATE

(Concord panels with software versions 1.0–1.6 display

USER CODES.)

2. Press B until the display shows OPTIONS, then press É.

The display shows DOWNLOADING ON/OFF (current

setting).

3. Press B twice and the display shows TOUCHPAD

BRIGHTNESS 2 (default setting).

4. Enter a setting from 0 (darkest background) to 3 (brightest

background), then press É.

5. The display flashes the entered selection, then stops after

pressing É and displays the new setting and brightness

level.

6. Exit user programming mode.

To adjust display contrast:

1. Enter configuration mode by pressing the D and 6 buttons

together for at least two seconds. The display shows DA

nnn.

2. Press and release the 1 and 2 buttons together

repeatedly, until the desired contrast level is displayed.

3. Press Ç and the display briefly shows DONE, then shows

the time and date.

Troubleshooting

Problem Action/Solution

Touchpad doesn’t
power up (no display
and no beeps when
buttons are pressed).

Check for correct wiring connections at
touchpad and panel terminals.

Make sure panel battery is connected
correctly and that the panel transformer is
plugged in.

Make sure panel transformer is not plugged
into an electrical outlet controlled by a switch.
Relocate transformer to an unswitched outlet
location, if necessary.

Touchpad display
appears blank, but
beeps sound when
buttons are pressed.

Check the touchpad display contrast setting.
It may be set to 0 (no display).

Touchpad display
shows a flashing *,
indicating a trouble
condition and system
doesn’t respond to
commands from
touchpad.

Check for correct bus wiring connections
(green and white wires) at touchpad and
panel terminals.

Make sure touchpad unit number is set to a
different number than all other bus devices. If
necessary, change the touchpad unit number
(see procedure on this page). (Concord
panels with software versions 1.0-1.6 only.)

Changing the touchpad unit number

(Concord

panels with software version 1.0-1.6 only)

Use the following guidelines when changing device unit

numbers to avoid communication conflicts between bus

devices and the panel:

All bus devices with DIP switches (LED Touchpads,

ESMs, HIMs, etc.) must be set to the desired unit number

before applying power and entering program mode.

Whenever possible, assign touchpad unit numbers before

all other panel programming.

To change the touchpad unit number:

1. At the touchpad, press and hold the D and 6 buttons

together for at least 2 seconds. The display should show

DA n, where n is the current touchpad unit number (000 -

015).

Note: At this time, the touchpad is in configuration mode

and no longer communicating to the panel. The system

may immediately indicate a bus failure. Ignore the failure

and continue with the procedure. The bus failure will clear

after successfully changing the touchpad unit number.

2. Press É. The display shows ENTER _.

3. Enter the desired three digit unit number (000 - 015), then

press É. The display shows DA n, where n is the new

touchpad unit number.

4. Do not use unit number 15 in Concord RF systems.

5. Press Ç to exit from the configuration mode.

Note: If the new touchpad unit number was previously

learned by the panel, communication between the

touchpad and the panel begins immediately. However, if

the new touchpad unit number has never been learned by

the panel, continue with step 6.

6. Force the panel to scan bus devices as follows:

For systems where this is the only installed touchpad,

remove panel AC and battery power, then re-apply

power.

For systems with more than one touchpad, go to

another system touchpad and enter 8 +

installer/dealer CODE (default = 4321) + 0 + 1. The

display

shows

SCANNING BUS DEVICES, then a

time and date display.

The touchpad and all other bus devices should operate

correctly and any bus failures should be cleared.

Note: If the panel still indicates a bus failure the panel may

have previously learned a unit number that is no longer

4

ATP1000 Touchpad/Display Installation Instructions