3 fan tray, 4 power entry modules (pems) – Cisco 6200 User Manual
Page 6
1
Hardware Description
78-5296-02
10/02/98
Cisco 6200 User Guide
1-6
Auxiliary Port
J40, a 9-pin female connector on the Cisco 6200 backplane, is an EIA/TIA-232 (RS-232) serial port
connecting to the management processor card (MPC). J40 is an auxiliary craft port that can be used
to connect devices such as terminals, modems, or laptop computers to the Cisco 6200. It is accessible
from the rear of the chassis. For a pinout list, see Appendix A, “Pin Assignments.”
Power Terminals
J17, J18, J19, and J20, located at the upper right corner of the rear panel, are screw terminals for
–48 VDC power input and return:
•
J17 is the –48V terminal for power circuit A.
•
J19 is the +48V (return) terminal for power circuit A.
•
J18 is the –48V terminal for power circuit B.
•
J20 is the +48V (return) terminal for power circuit B.
Power circuit A is connected to the power entry module (PEM) on the left (as you face the front of
the chassis); power circuit B is connected to the PEM on the right.
Unused Connectors
The Cisco 6200 backplane contains several connectors and a jumper that are not used in the current
release. See Appendix A, “Pin Assignments,” for a list of the unused items.
1.2.3 Fan Tray
The fan tray, located at the bottom of the chassis, houses eight fans that maintain proper temperatures
inside the chassis, plus an air filter. The filter should be removed and cleaned periodically. Refer to
Chapter 6, “Preventive Maintenance,” for complete information on cleaning the air filter.
Caution
The Cisco 6200 cooling fans must run continuously. The system may suffer thermal damage if the
fans stop for more than 10 minutes. (At ambient temperatures above 104 F(40 C),thermal damage may occur
sooner.)
1.2.4 Power Entry Modules (PEMs)
One or two PEMs distribute DC power to the chassis. The Cisco 6200 needs only one active PEM
to operate; if two PEMs are installed, the second PEM’s power source serves as a hot backup to the
first PEM’s power source.
Each PEM is connected to a single DC power source. For power redundancy, two PEMs must be
installed, and two separate DC power sources must be connected to the chassis. If one power source
is connected, only one PEM is required. There is no benefit to connecting two power sources to a
chassis with one PEM, or to installing two PEMs in a chassis with one power source.
The PEMs reside at the top of the Cisco 6200 chassis, and they are installed and accessed from the
front. DC power (–48V) enters the chassis through screw terminals on the rear panel of the chassis.
The PEMs receive power through the backplane and internal cabling.
The power bay on the left is wired to power circuit A; the bay on the right is wired to power circuit B.
(The circuits are identified at the power terminals on the backplane.)