21

Liquid Line Filter Drier

The factory-provided reversible filter drier is specifically de-

signed to operate with Puron®. Replace the filter drier with

factory-authorized components only with a filter drier with

desiccant made from 100% molecular sieve grade XH-11. Fil-

ter drier must be replaced whenever the refrigerant system is

opened.
When removing a filter drier, use a tubing cutter to cut the drier

from the system. Do not unsweat a filter drier from the sys-

tem. Heat from unsweating will release moisture and contami-

nants from drier into system.

Field Refrigerant Access Ports

Field service access to refrigerant pressures is through the

access ports located at the service valves (see Figs 24, 26 and

28). These ports are ¼-in SAE Flare couplings with Schrader

check valves and service caps. Use these ports to admit

nitrogen to the field tubing during brazing, to evacuate the

tubing and evaporator coil, to admit initial refrigerant charge

into the low-side of the system and when checking and

adjusting the system refrigerant charge. When service activities

are completed, ensure the service caps are in place and secure;

check for leaks. If the Schrader check valve must be removed

and re-installed, tighten to 2-3 in-lbs (23-34 N-cm).

Outdoor Coil Metering Devices

The metering devices are multiple fixed–bore devices (Acu-

trol™) swaged into the horizontal outlet tubes from the liquid

header, located at the entrance to each evaporator coil circuit

path. These are non–adjustable. Service requires replacing the

entire liquid header assembly.

To check the indoor coil, disconnect the supply fan signal

(A04-A06 direct-drive fans) or contactor (IFC) coil, then start

the circuit in a Cooling Mode (jumper R to Y1 or Y2) and ob-

serve the frosting pattern on the face of the indoor coil. A frost

pattern should develop uniformly across the face of the indoor

coil starting at each tube at the Acutrol nipple locations.
To check the outdoor coil, disconnect the outdoor fan motor.

Start the circuit in a Heating Mode (jumper R to W1 or W2)

and observe the frost pattern on the face of the outdoor coil.
Failure to develop frost at an outlet tube can indicate a plugged

or a missing orifice.

Refrigerant System Pressure Access Ports

There are two access ports in each circuit - on the suction tube

near the compressor and on the discharge tube near the com-

pressor. These are brass fittings with black plastic caps. The

hose connection fittings are standard 1/4 SAE Male Flare cou-

plings.
The brass fittings are two-piece High Flow valves, with a re-

ceptacle base brazed to the tubing and an integral spring-closed

check valve core screwed into the base. (See Fig. 20.) This

check valve is permanently assembled into this core body and

cannot be serviced separately; replace the entire core body if

necessary. Service tools are available from RCD that allow the

replacement of the check valve core without having to recover

the entire system refrigerant charge. Apply compressor refrig-

erant oil to the check valve core's bottom o-ring. Install the fit-

ting body with 96 +/-10 in-lbs of torque; do not overtighten.

Fig. 20 — CoreMax Access Port Assembly

1/2-20 UNF RH

30°

0.596

.47

5/8” HEX

SEAT

CORE

WASHER

DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY

7/16-20 UNF RH

O-RING

45°

1/2" HEX

This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.

(Part No. EC39EZ067)