Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data

UN

IT

NOM.

V---Ph---Hz

IFM

TYPE

COMBUSTION

FAN MOTOR

POWER

EXHAUST

NO C.O. or UNPWR C.O.

FLA

FLA

NO P.E.

w/ P.E. (pwrd fr/ unit)

MCA

FUSE

or

HACR

BRKR

DISC. SIZE

MCA

FUSE

or

HACR

BRKR

DISC. SIZE

FLA

LRA

FLA

LRA

48TC*

D

16

208/230---3---60

STD

0.48

3.8

68.3

80

71

396

72.1

80

76

400

MED

70.8

80

74

413

74.6

90

79

417

HIGH

81.2

100

86

432

85.0

100

91

436

460---3---60

STD

0.25

1.8

34

45

35

234

35.8

45

37

236

MED

35.0

45

37

243

36.8

45

39

245

HIGH

40.8

50

43

252

42.6

50

45

254

575---3---60

STD

0.24

3.8

26.5

30

28

184

30.3

40

32

188

MED

26.5

30

28

184

30.3

40

32

188

HIGH

32.7

40

35

196

36.5

45

39

200

Table 10 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)

UN

IT

NOM.

V---Ph---Hz

IFM

TYPE

COMBUSTION

FAN MOTOR

POWER

EXHAUST

w/ PWRD C.O.

FLA

FLA

NO P.E.

w/ P.E. (pwrd fr/ unit)

MCA

FUSE

or

HACR

BRKR

DISC. SIZE

MCA

FUSE

or

HACR

BRKR

DISC. SIZE

FLA

LRA

FLA

LRA

48TC*

D

16

208/230---3---60

STD

0.48

3.8

73.1

80

77

401

76.9

100

81

405

MED

75.6

100

80

418

79.4

100

84

422

HIGH

86.0

100

92

437

89.8

100

96

441

460---3---60

STD

0.25

1.8

36.2

45

38

236

38

50

40

238

MED

37.2

50

39

245

39.0

50

41

247

HIGH

43.0

50

46

254

44.8

50

48

256

575---3---60

STD

0.24

3.8

28.2

35

30

186

32

40

34

190

MED

28.2

35

30

186

32

40

34

190

HIGH

34.4

40

37

198

38.2

45

41

202

Legend and Notes for Table 10

LEGEND:

BRKR

--- Circuit breaker

CO

--- Convenience outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

P.E.

--- Power exhaust

PWRD CO

--- Powered convenient outlet

UNPWR CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and

combination load equipment (refer to NEC Articles 430 and

440), the overcurrent protective device for the unit shall be

fuse or HACR breaker. Canadian units may be fuse or circuit

breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the following formula to de-

termine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

48TC

**16