Configuration Screens (cont)

*Default values from factory.

NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::HIR: Heat Interlock Relay
Output Logic Type

Normal

LogType

Minimum Off Time

60

sec

MinOff

Minimum On Time

60

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::PUMP: Pump Request
Output Logic Type

Normal

LogType

Minimum Off Time

5

sec

MinOff

Minimum On Time

5

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::SF: Supply Fan/VFD
Output Logic Type

Normal

LogType

Minimum Off Time

30

sec

MinOff

Minimum On Time

60

sec

MinOn

Delay Time

10

sec

DlyTim

OMNIZONE::TOWER: Cooling Tower Request
Output Logic Type

Normal

LogType

Minimum Off Time

5

sec

MinOff

Minimum On Time

5

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::TRMCT: VAV Terminals Control
Output Logic Type

Normal

LogType

Minimum Off Time

60

sec

MinOff

Minimum On Time

60

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::TRMOP: VAV Terminals Open MAX
Output Logic Type

Normal

LogType

Minimum Off Time

5

sec

MinOff

Minimum On Time

5

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::VENTR: Ventilation Request
Output Logic Type

Normal

LogType

Minimum Off Time

3

sec

MinOff

Minimum On Time

3

sec

MinOn

Delay Time

5

sec

DlyTim

OMNIZONE::WARN: Non Critical Fault
Output Logic Type

Normal

LogType

Minimum Off Time

4

sec

MinOff

Minimum On Time

4

sec

MinOn

Delay Time

10

sec

DlyTim

OMNIZONE::DSALM01: Duct High Pressure
Monitored Input Point

DHS

Name

Comparison Point

SENSDI00

Name

Alarm Inhibit Point

SENSDI00

Name

Discrete Check

Alarm Logic

Normal

AlmLogic

Enable Delay Time

15

sec

DlyTim

Persistence Time

10

sec

Persist

Alarm Processor

Alarm Processing

Enable

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

Type

Alarm Level

1

AlmLevel

Alarm Source

5

AlmSrc

Alarm Routing

11010000

AlmRtg

Alarm Description Index

0

AlmDesc

Alarm Message - Part 1

Duct High Static

Message

Alarm Message - Part 2

Pressure

Message

Alarm Message - Part 3

Message

Alarm Message - Part 4

Message

Power on Delay

0

sec

PowerUp