Mr-dt – Keri Systems MR50 User Manual

Page 2

Advertising
background image

Mercury Security Corporation © 2014

MR50

DOC 10107-0009

REV 2.03

Page 2

Reader Wiring:

Door Strike Relay Wiring:

Two Form-C contact relays are provided for controlling door strike or other devices. The contact
ratings are 5 A for relay K1 and 1 A for relay K2. Load switching can cause abnormal contact wear
and premature contact failure. Switching of inductive loads (strike) also causes EMI (electromagnetic
interference) which may interfere with normal operation of other equipment. To minimize premature
contact failure and to increase system reliability, contact protection circuit must be used. The
following two circuits are recommended. Locate the protection circuit as close to the load as possible
(within 12 inches [30 cm]), as the effectiveness of the circuit will decrease if it is located far away.


ADDRESS 0

MR-DT

RS-485 MODE

9600 BAUD

READER PORT
2-WIRE RS-485

12Vdc (RED) (1)

TR+ (BLUE) (3)

TR- (GRAY) (4)

GROUND (BLACK) (2)

VO

TB4

GND
BZR

D0/DAT/T-

D1/CLK/T+

LED

RED (1)

GRN (2)

BLK (6)
ORG (5)

WHT (3)

BRN (4)

READER PORT
2-WIRE RS-485

GND

D0/DAT/T-

D1/CLK/T+

VO

LED

TB4

BZR

MR

-10/20

R

EA

DE

R

DATA1/DATA0 - CLOCK/DATA

2-WIRE RS-485

Diode Selection:
Diode current rating: 1x strike current
Diode breakdown voltage: 4x strike voltage
For 12 Vdc or 24 Vdc strike, diode 1N4002
(100V/1A) typical

MOV Selection:
Clamp voltage: 1.5x Vac RMS.
For 24 Vac strike, Panasonic:
ERZ-C07DK470 typical

 

TB3

K2

K1

C

NC

NO

C

NO

NC

K2

K1





TB3

K2

K1

C

NC

NO

C

NO

NC

K2

K1

