Mercury Security Corporation © 2014

MR50

DOC 10107-0009

REV 2.03

Page 3

3. Communication to a Controller:

The MR50 communicates to a Mercury Security intelligent controller (EP2500 for example) via a half
duplex multi-drop 2-wire RS-485 interface. The total cable length is limited to 4,000 feet (1,219
meters). Shielded cable of 24 AWG with characteristic impedance of 120 ohm is specified for the 2-
wire RS-485 interface. The last device on each end of the communication line should have the
terminator installed (set jumper J4 on).

Address, Baud Rate and Encryption Configuration Jumpers:

Each Interface (MR50, MR52, etc.) must be configured to have a unique address and correct baud
rate. The address and baud rate are selected by installing the specified jumpers.

Note 1: Firmware revisions prior to 1.39.1, the 115200 baud rate setting is 2400 baud.

Note 2: Firmware revisions prior to 1.39.1, jumper 8 is not defined, remove jumper.

MR-50

CONTROLLER

TO ADDITIONAL

SIO UNITS

J3

7

TR+

TB1

3

J2

2

1

6

5

4

GND

TR-

DAT

VO

D0

J4

8

J3

7

TB1

3

2

J2

1

6

5

4

TR+

GND

TR-

8

J4

DAT

VO

D0

TR-

GND

TR+

MR-50

LAST UNIT ON
COMMUNICATION
LINE - TERMINATOR
INSTALLED