Quick Start Guide

LC-202P/LC-208P

5.2.3

Reader Daisy-Chain

One Proximity reader is shared by all elevator control panels in an elevator control application. The
main reader connections are made to a primary LC-202P elevator panel. All other reader
connections to the remaining LC-202P panels are made per the following rules.

1. The reader antenna line must be daisy-chained to all other elevator panel antenna inputs – Pin 1

of TB-5 and TB-6 on the LC-202P panels.

2. The reader ground line must be daisy-chained to all other elevator panel antenna grounds to

provide a standard ground reference for all panels – Pin 4 of TB-5 and TB-6 on the LC-202P
panels.

3. The reader shield line must be connected to the A-floor controller antenna ground at the master

elevator panel ONLY (Pin 4 of TB-5 on the master LC-202P panel).

4. The reader power line must be connected to the master elevator panel ONLY (Pin 3 of TB-5 on

the master LC-202P panel).

Make the reader connections per the information in Table 4 and Figure 7 on page 13.

Table 4: Daisy-Chained Reader

Connections

TB-5/TB-6 Pin

Description

1

Antenna

2

Beeper

3

Power

4

Ground

5

Green LED

6

Red LED

7

- no connection -