Commercial Kit from the manufacturer.

Part numbers for the low profile terminals to cover

the vent and combustion air openings are shown in

Table 6.

SECTION 3.

Gas Supply and Piping

3.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The MT2P’s gas train allows the user to pipe the

gas from either the right side or the left side of the unit.

As shipped, the left side of the gas train is capped off,

and there is a manual valve on the right side. If desired,

the manual valve may be switched with the cap on the

opposite side to accommodate alternate installations.

Review the following instructions before

proceeding with the installation.
1. Verify that the appliance is fitted for the proper

type of gas by checking the rating plate. Laars

Heating Systems appliances are normally

equipped to operate at elevations up to 2000 feet

(610m). MT2P appliances may be adjusted to

operate properly at higher elevations; however,

input will be reduced if the heating value of the

gas supply is below sea level values.

2. The maximum inlet gas pressure must not exceed

13" W.C (3.2kPa). The minimum inlet gas

pressure is 5" W.C. (1.2kPa).

3. Refer to

Table 7

, size supply.

4. Run gas supply line in accordance with all

applicable codes.

5. Locate and install manual shutoff valves in

accordance with state and local requirements.

6. A sediment trap must be provided upstream of the

gas controls.

7. All threaded joints should be coated with

piping compound resistant to action of liquefied

petroleum gas.

8. The appliance and its individual shutoff valve

must be disconnected from the gas supply piping

during any pressure testing of that system at test

pressures in excess of 1/2 PSIG (3.45kpa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas supply

piping system at test pressures equal to or less

than 1/2 PSIG (3.45kpa).

10. The appliance and its gas connection must be leak

tested before placing it in operation.

11. Purge all air from gas lines.

Caution

Do not use open flame to check for leaks.

NOTE: The MT2P appliance and all other gas

appliances sharing the gas supply line must be firing at

maximum capacity to properly measure the inlet supply

pressure. The pressure can be measured at the supply

pressure port on the gas valve. Low gas pressure

could be an indication of an undersized gas meter,

Figure 5. Pool Heater Piping.

The MT2P Pool Heater is shipped with a field-installed mixing system, and must be piped in prima-

ry-secondary style, as shown. A remote pool temperature sensor and remote pool temperature high

limit are wired to the MT2P, to be mounted in the pool water loop, as shown.