Laars heating systems – LAARS Mighty Therm2 MT2P (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 8

Advertising
background image

LAARS Heating Systems

Page 8

Figure 3. Combustion Air and Vent Through Side Wall.

U.S. Installations (see note 1)

Canadian Installations (see note 2)

A= Clearance above grade, veranda, porch,

12 inches (30 cm)

12 inches (30 cm)

deck, or balcony

See note 6

See note 6

B= Clearance to window or door that may be 4 feet (1.2 m) below or to side of opening;

36 inches (91 cm)

opened

1 foot (30 cm) above opening

C= Clearance to permanently closed window See note 4

See note 5

D= Vertical clearance to ventilated soffit located

above the terminal within a horizontal

See note 4

See note 5

distance of 2 feet (61cm) from the center line

of the terminal

E= Clearance to unventilated soffit

See note 4

See note 5

F= Clearance to outside corner

See note 4

See note 5

G= Clearance to inside corner

See note 4

See note 5

H= Clearance to each side of center line

3 feet (91 cm) within a height 15 feet above

extended above meter/regulator assembly See note 4

the meter/regulator assembly

I= Clearance to service regulator vent outlet See note 4

3 feet (91 cm)

J= Clearance to nonmechanical air supply inlet

to building or the combustion air inlet to

4 feet (1.2 m) below or to side of opening;

36 inches (91 cm)

any other appliance

1 foot (30 cm) above opening

K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)

6 feet (1.83 m)

horizontally

L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in this location

driveway located on public property

for category IV appliances.

for category IV appliances.

M= Clearance under veranda, porch, deck,

See note 4

12 inches (30 cm) (see note 3)

or balcony

Notes:

1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the

gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas

supplier.
6. IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have more

specific requirements, and must be consulted.

*When vent terminal is less than 10 feet (3m) horizontally

from a forced air inlet, the terminal must be at least 3 feet

(0.9m) above the air inlet.