LAARS Heating Systems

Page 4

Figure 3. The User Interface.

3.1 Digital Display

the centerpiece of the User Interface is the Digital

Display. All of the needed parameters of the Mascot LX

can be viewed and adjusted on this Digital Display. All

controls can be adjusted using the ‘select’ button and the

Up and Down arrows.

3.2 Controller Modes

three control modes can be displayed:

USER, INSTALLER, AND SERVICE.


3.2A The USER Mode

the User Mode is for a homeowner or service

technician to adjust the most common operating

parameters. In the UseR Mode, when the boiler is

on and operating normally, the UseR can scroll Up

and Down using the Arrow Keys. of the 7 viewable

parameters, 4 can be adjusted (depending on if they are

installed). the UseR adjustable parameters are the outlet

temp, DHW setpoint, and outdoor Air temp. If the

system setpoint is installed, it can be adjusted, but then

the outlet temperature can no longer be adjusted.

these parameters can be adjusted in the UseR

Mode by pressing the ‘select/oK’ button (while in that

parameter) and then using the Up and Down arrows to

set to the desired temperature.

once the desired parameter is displayed, always

press ‘select/oK’ again to save that setting.

3.2B The INSTALLER Mode

the Installer Mode is an extensive set of

parameters that can be changed to suit the individual

installation and should only be accessed by a trained

service technician or installer.

to access the InstALLeR Mode, hold

‘Select/OK’ and the down ˅ arrow key simultaneously

3. The User Interface and the

Digital Display

until U00 is displayed. Press ‘select/oK’ again and then

release. Change the value to 15 and then press ‘select/oK’

again. the InstALLeR Mode Parameters will then be

accessible by pressing the Up or Down arrows.

note: For the full list of ‘Installer Mode

Parameters’ and full details on using the User Interface,

please see the Mascot LX Installation and operating

Manual (Document 1285), available on laars.com

to change the value of that parameter, press select/

oK button again. the parameter will blink. Pressing

the Up or Down arrows will increase or decrease the

parameter value. The value will be confirmed by pressing

select/oK button and the blink will stop.

the parameter value will return to the previous setting

if you press the Cancel button.

otherwise, exit InstALLeR Mode by pressing and

holding ‘select/oK’ for 3 seconds.

3.2C The SERVICE Mode

the service Mode is intended for servicing and

troubleshooting of the unit by a Mascot LX trained

service technican.

the ‘seRVICe’ Mode can be activated by pressing

and holding the ‘select/oK’ button and ‘Up Arrow’

simultaneously for five seconds. With an active call for

heat, the boiler will light and run at 100% of firing rate.

the boilers input can be adjusted in 20% rate increments

by pressing the ‘Up’ or ‘Down’ Arrows. You can also

toggle between Maximum Rate and Minimum Rate by

pressing the ‘select/oK’ button. to exit seRVICe Mode

depress and hold the ‘Select/OK’ button for five seconds.

3.3 Ignition Control- Sequence of Events

1. Call for heat

2. safety chain check

3. Fan starts.

4. Prepurge timer is started.

5. Pre ignition time of 2 seconds to check the flame

sensor operation and status.

6. trial for ignition starts by energizing the spark

ignition and opening the gas valve. If flame is

sensed, the control starts the burner to satisfy the

demand. If the flame is not established the control

enters a ‘retry’ starting again from step 2. If flame

is not established after 4 attempts, the control will

lockout with an E12 error code.

7. Call for heat complete.

8. Gas valve off.

9. Fan and pump over run times active to purge the system.

the sequence is the same for DHW or Central

Heat modes. Upon a call for Central Heat, the 3-way

valve will shift position, allowing boiler water to enter