LAARS Mascot LX MLXC 175 MBH - Users Manual User Manual

Page 7

Advertising
background image

User’s Manual - Mascot LX Boilers and Water Heaters

Page 5

the building’s heating loop. only after the value shifts

position will the firing sequence begin.

3.4 Modulation Control

the control uses a PID algorithm to adjust

the firing rate of the boiler as the control point is

approached. the goal of the control is to operate at a

minimum firing rate to match the load on the appliance.

3.5 Pump Control

the boiler pump is active anytime there is a call for

heat applied to the control. When there is a central heat

call the system pump relay is active. If there is a DHW

call while the central heat call is active the system pump

turns off. this happens because of domestic hot water

priority, which forces the control to satisfy the domestic

water demand prior to the hydronic demand. When the

last heat demand is satisfied the boiler pump enters an

overrun time.

3.6 High Limit

the control uses a dual thermistor sensor to

monitor the Mascot LX’s maximum temperature. the

high limit sensor is installed in the outlet water. A dual

thermistor sensor is used, so that the two temperatures

can be monitored and compared to confirm accuracy.

The control will automatically reduce the firing of the

Mascot LX to prevent the high limit from tripping. the

high limit setpoint is not adjustable.

3.7 Stack Temperature

the stack temperature is a dual thermistor sensor

and is limit rated. the control compares each of the

temperature readings to determine accuracy. the stack

sensor is used as a limiting feature to avoid excessive

temperatures in the venting.

3.8 Domestic Hot Water Temperature

the domestic hot water temperature sensor is used

to control the DHW temperature. the DHW setpoint can

be adjusted through the Base / Home state and the User

Mode. on LX ‘C’ or Combi models, the DHW sensor is

pre-installed in the DHW exchanger. on LX ‘H’ or Heat

models the DHW can be can be controlled by an aquastat

or optional DHW sensor installed in an indirect tank.

connected. Repeat this process for terminal B and

GnD.

To configure the control system, identify which

boiler is going to be the “master” boiler for the cascade

system and navigate to installer parameter P06,

“Cascade Address”. set the address to “0” and press

and hold “select”. When “auto cfg” appears on the

display press “select” to start the auto configuration

process. The auto configuration process will find all

boilers connected to the “master” boiler and assign

addresses. When auto configuration is complete the

display should show “boilr #” where # is the total

number of boilers found in the cascade system.

The final steps are to set the individual setpoints

in the cascade system, which include P07 “Cascade

setpoint”, P08 “Cascade off Hysteresis” and P09

“Cascade on hysteresis”. these variables must be set to

the appropriate values for the installation. When setting

P09 “cascade on hysteresis” the value should not be

less than P08 “Cascade off Hysteresis” as P09 references

the off point (P07+ P08) as the starting point for the on

hysteresis. An example of this is shown below.

Correct settings:

P07 = 120°F

P08 = 10°F

P09 = 20°F

With these setting the modulation point is 120°F

the off point is 120°F + 10°F = 130°F

the on point is 130°F – 20°F = 110°F

Incorrect settings:

P07 = 120°F

P08 = 10°F

P09 = 5°F

With these setting the modulation point is 120°F

the off point is 120°F + 10°F = 130°F

the on point is 130°F – 5°F = 125°F

In this case the boiler is turning back on prior to

reaching the modulation point, which could lead to

short cycling.

3.9.1 Cascade Manual Configuration

In some applications it may be necessary to

configure the cascade system manually. To do this, the

boilers should be wired as shown in the Auto Cascade

section of the manual. then each individual control in

the cascade must have a specific address assigned by

adjusting P06 “ Cascade address” on each boiler. to

start, identify the boiler that will be the “master” boiler.

navigate to parameter P06 “cascade address” set to

“0” and press “select” (do not press and hold select).

then press and hold select.

Repeat this process for each boiler in the cascade

setting each address to a unique number.

the last step is to adjust all of the setpoints

for the installation application as shown in the Auto

cascade section of the manual.

3.9 Cascade Auto Configuration

to operate up to 8 boilers in cascade, the boilers

must be “daisy chained” together using Modbus

terminals A, B and GnD, located on the boilers terminal

block. the wiring should be completed with at least

three wire shielded cable with ground. the ground wire

should be connected to a suitable chassis ground on one

end of the daisy chain only. Wire each boilers terminal

A in series with the next boilers terminal A until all are

Advertising