LAARS 9600 CB - Installation, Operation and Maintenance Instructions User Manual

Page 3

Advertising
background image

9600 CB

Page 3

Automatically Fired Boilers, ANSI/ASME CSD-1.

In the Commonwealth of Massachusetts, this

appliance must be installed by a licensed plumber or
gas fitter.

1.2 Materials Installer Must Provide

SECTION 1.
Introduction and Unpacking

1.1 General Instructions

It is important for you to take a few minutes to

review this Installation and Operating Instructions
manual before you begin installation. This will make
installing and operating the unit easier and faster.

Direct vent-sealed combustion:
The 9600 CB boiler does not and should not take

combustion air from inside the building. All of the air
is drawn in from outdoors through a 3-inch diameter
plastic pipe. 3" PVC, ABS or CPVC pipe is used for
air intake and exhaust venting. (PVC, ABS not
permitted for CB-M2-250 exhaust).

No chimney....flue....or draft inducer required.

Because this is a sealed combustion, forced draft unit,
it does not require, and must not be connected to a
chimney, existing venting system, or draft inducer.

Caution

Connection of this vent to a chimney, existing venting
system, or draft inducer will result in poor and possibly
dangerous operation.

The supplied vent terminations are designed to

be installed through the nearest outside wall.

The CB boiler is protected against over

pressurization. A 50 PSI pressure relief valve is fitted
to all units and a 125 PSI valve is optional. It is
installed in the dedicated fitting on the back of the
boiler.

IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13" WC.

A high quality circulator is built into the CB

boiler and will provide sufficient head to circulate
water to the supply and return headers. An external
circulator is required to circulate water to and from
baseboard or fan coil units (secondary loop).

All installations must be made in accordance

with the 1). American National Standard Z223.1-
Latest Edition “National Fuel Gas Code” or 2). CSA
B149.1 "Installation Codes for Gas Burning
Appliances and Equipment" and with the requirement
of the local utility or other authorities having
jurisdiction. Such applicable requirements take
precedence over the general instructions contained
herein.

All electrical wiring is to be done in accordance

with the local codes, or in the absence of local codes,
with: 1). The National Electrical Code ANSI/NFPA
No. 70-latest Edition, or 2). CSA STD. C22.1
"Canadian Electrical Code - Part 1". This appliance
must be electrically grounded in accordance with
these codes. Where required by the authority having
jurisdiction, the installation must conform to the
Standard for Controls and Safety Devices for

a.

Total combined feet allowed for intake and
exhaust vent pipe per instructions. The following
are acceptable materials for intake and exhaust
vents:

b.

Electrical connection to a 120VAC/15Amp
service.

c.

Gas connection that will provide 250 cubic feet/
hour at 4 to 13 inch water gauge pressure.

d.

Condensate drainage: a floor drain is preferred, a
condensate pump can be used if required.

e.

Miscellaneous copper fittings and bronze valves
will be required to complete the piping system.

M ode ls 150-200

M ode l 250

3-inch or 4-inch PVC
schedule 40 pipe per ASTM
D-1785 std.

3-inch or 4-inch PVC
schedule 40 pipe per ASTM
D-1785 std.

3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.

3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.

3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std.
or ASTM F-628 std.

3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std.
or ASTM F-628 std.

3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.

3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.

3-inch or 4-inch AL29-4C
stainless steel complying
with UL std. 1738.

3-inch or 4-inch AL29-4C
stainless steel complying
with UL std. 1738.

M ode ls 150-200

M ode l 250

3-inch or 4-inch PVC
schedule 40 pipe per ASTM
D-1785 std.

3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.

3-inch or 4-inch PVC DWV
pipe per ASTM D-2665 std.

3-inch or 4-inch AL29-4C
stainless steel complying
with UL std. 1738.

3-inch or 4-inch ABS-DWV
pipe per ASTM D-2661 std.
or ASTM F-628 std.
3-inch or 4-inch CPVC
schedule 40 or 80 pipe per
ASTM F441 std.
3-inch or 4-inch AL29-4C
stainless steel complying
with UL std. 1738.

Acce ptable Exhaust Ve nt Pipe M ate rial

Acceptable Intake Pipe Material

Advertising