Laars heating systems – LAARS 9600 CB - Installation, Operation and Maintenance Instructions User Manual

Page 6

Advertising
background image

Page 6

LAARS Heating Systems

U.S. Installations (see note 1)

Canadian Installations (see note 2)

A=

Clearance above grade, veranda, porch,

12 inches (30 cm)

12 inches (30 cm)

deck, or balcony

B=

Clearance to window or door that may

12 inches (30 cm)

36 inches (91 cm)

be opened

C=

Clearance to permanently closed window

See note 4

See note 5

D=

Vertical clearance to ventilated soffit located
above the terminal within a horizontal

See note 4

See note 5

distance of 2 feet (61cm) from the
center line of the terminal

E=

Clearance to unventilated soffit

See note 4

See note 5

F=

Clearance to outside corner

See note 4

See note 5

G=

Clearance to inside corner

See note 4

See note 5

H=

Clearance to each side of center line

See note 4

3 feet (91 cm) within a height 15 feet above

extended above meter/regulator assembly

the meter/regulator assembly

I=

Clearance to service regulator vent outlet

See note 4

3 feet (91 cm)

J=

Clearance to nonmechanical air supply inlet

12 inches (30 cm)

36 inches (91 cm)

to building or the combustion air inlet to
any other appliance

K=

Clearance to a mechanical air supply inlet

3 feet (91 cm) above if within 10 feet (3 m)

6 feet (1.83 m)

horizontally

L=

Clearance above paved sidewalk or paved

Vent termination not allowed in this location

Vent termination not allowed in this location

driveway located on public property

for category IV appliances.

for Category IV appliances.

M= Clearance under veranda, porch, deck,

See note 4

12 inches (30 cm) (see note 3)

or balcony

Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.

2. In accordance with the current CAN/CGA-B149 Installation Codes.

3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of

the gas supplier.

5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas

supplier.

Figure 5A. Vent terminal clearances.