9600 HWG Water Heater

Page 17

6.2 9600 Overheats Quickly or Knocks

During Operation

Boiling noise in combustion chamber.

1.

Air in combustion coil or in pump: Purge

system.

2.

Pump failure or control failure.

3.

9600 HWG lime buildup in primary heat

exchanger.

4.

Restriction in storage tank piping.

5.

Defective thermostatic valve element.

6.3 Delayed Ignition

Unit starts or stops with a “pop”.

1.

Wrong gas orifice for fuel or air orifice size.

2.

LP-Gas regulator lock up 3" or greater above run

pressure: correct regulator and check gas pipe

sizing against piping chart in installation manual.

Set regulator for maximum run pressure of 9".

3.

Remove blower and inspect flame holder

(burner) for hole.

4.

Check that the blower flanges and gas piping are

sealed.

6.4 Occasional Lockouts

Requires interruption of power or reset of

safety limit to re-start.

1.

Air in system causes safety limit to open. Vent

air from system and eliminate source of air.

2.

Condensing in primary heat exchanger or

moisture in combustion chamber.

a.)

defective element in thermostatic valve.

b.) improper installation of intake terminal.

c.)

blocked condensate and condensate

overflow system.

3.

Poor Combustion - check CO2 or O2.

4.

Intermittent ignitor failure: defective ignitor

gasket allows ignitor base to overheat.

5.

Occasional failure of blower: red “PURGE” light

will be flashing.