LAARS Heating Systems

1.3 Unpacking

The 9600 HWG Water Heater is shipped in a

single carton with the following standard components

on top of the unit (see Figure 1).

1) Exhaust terminal

2) Intake terminal

3) Vent terminal backing plate (4)

4) Hubless coupling reducer

5) Hubless coupling (2)

Minimum

Recommended

Clearances

Clearance for

From

Accessibility

Combustible

and Venting

Construction

BOTH

AGA

CGA

Left Side

1"

6"

48"

Right Side (Controls)

1"

12"

24"

Top

1"

14"

24"

Back

1"

9"

24"

Front

1"

24"

48"

Vent

0"

Table 1. Location clearances.

Figure 1. Contents of shipping package.

1.

Remove all packing and tie-down materials.

2.

Check contents of the carton against items

shown above.

SECTION 2.
Locating and Clearances

2.1 Locating the 9600 HWG

The appliance should be located in an area

where leakage of any connections will not result in

damage to the area adjacent to the appliance or to

lower floors of the structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The unit is design certified by AGA / CGA for

installation on combustible flooring; in basements; in

closets, utility rooms or alcoves. It must not be

installed on carpeting.

The location for the unit should be chosen with

regard to the vent pipe lengths, external plumbing,

ventilation of operating components and accessibility

for service and cleaning.

If there is potential for snow accumulation in your

area, both the vent terminals should be installed at an

appropriate level above grade (see Figures 2 and 3).

The following dimensions and requirements

should be met when choosing the location for the unit

(see Table 1):

Figure 2. Suggested vent terminal installations.

2.2 Locating the Unit for Proper Venting

Distance from the Outside Wall or
Roof Termination

Intake

Exhaust

Maximum run:

Maximum run:

3" pipe size

3" pipe size

55 equivalent feet

55 equivalent feet

4" pipe size

4" pipe size

85 equivalent feet

85 equivalent feet

Minimum run:

Minimum run:

11 equivalent feet

21½ equivalent feet

Intake Terminal is

Exhaust Terminal is

P/N 2400-102.

P/N 2400-104.

Equivalent feet is determined by adding 10

linear feet for each 90° elbow and 5 linear feet for

each 45° elbow to be installed to the actual linear feet

of pipe required.

Example: 8' of pipe, 2 x 45° elbows and a 90°

elbow.

Equivalent Feet: 8' + (2 x 5') + (1 x 10') = 28.