LAARS HWG-M2-250 - Installation, Operation and Maintenance Instructions User Manual

Page 6

Advertising
background image

Page 6

LAARS Heating Systems

Length

Capacity of Pipe in MBTU/h

of

(.6 Specific Gravity)

Pipe

3/4"

1"

1-1/4"

10'

278

520

1,050

20'

190

350

730

30'

152

285

590

40'

130

245

500

50'

115

215

440

75'

93

175

360

100'

79

150

305

150'

64

120

250

Additional length to be added for each tee or bend:

1.7'

2.2'

2.7'

piping during any pressure testing of that system

at test pressures in excess of 1/2 psig (3.45kpa).

It must be isolated from the gas supply system

by closing its individual manual shutoff valve

during any pressure testing of the gas supply

piping system at test pressures equal to or less

than 1/2 PSIG (3.45kpa).
Failure to do so will possibly result in damage to

the gas control system.

8.

The 9600 HWG Water Heater and its gas

connections must be leak tested before placing

the unit in operation.

9.

Purge all air from gas lines.

3.3 Connecting Water System Piping,

Fittings & Accessories

Installing tank & piping

The 9600 HWG can be used with several

different types of readily available storage tanks. A

bronze circulating pump is built into the appliance.

The pump draws water from the storage tank and

pumps the water through the heater and back into

the tank.
Position the storage tank(s).

At the previously selected locations, position the

storage tank(s). Use Table 3 to determine the pipe size

necessary to provide adequate flow between the 9600

HWG and the tank(s).
Hot water outlet piping, fittings, and accessories.

1.

Begin piping to the tank from the hot water

outlet at the top of the 9600 HWG cabinet.

2.

Pipe the outlet from the relief valve (located on

top of the unit) such that any discharge from the

relief valve will be conducted to a suitable place

for disposal when relief occurs. Do not reduce

line size or install any valves in this line. The

line must be installed to allow complete drainage

of both the valve and the line.

3.

Install a shut off valve in the piping between the

thermometer fitting and the tank.

The following steps are recommended for vent

installation:
1.

Obtain the necessary 3" or 4" diameter plastic

piping and fittings as determined beforehand.

2.

Position unit at previously selected location.

3.

Unpack vent terminals and vent terminal backing

plates.

4.

Cut holes in outside wall for vent terminals in

the previously selected locations.

5.

Mount the vent terminals’ backing plates.

6.

Fit all of the vent pipes together without

cementing. Make sure that there are no water

traps and that any pitch is inclined back towards

the boiler.

7.

Make sure that the flexible vent connections at

the unit fit properly.

8.

Begin cementing the intake and exhaust pipes,

start at the vent terminals and work back towards

the appliance. Note that the intake terminal is a

90 degree elbow fitting that is designed to face

down.

9.

Support both intake and exhaust pipes with

hangers.

DO NOT RELY ON 9600 HWG TO SUPPORT
PIPES.

Horizontal runs must be supported adjacent to

each fitting and at 5ft. intervals between fittings.

ABS pipe must be supported at 3ft. intervals.

10. Tighten the flexible couplings to connect the

water heater to the vent pipes.

3.2 Connecting Gas to the 9600 HWG

Water Heater

1.

The water heater requires gas at an inlet gas

pressure of at least 4" WC and no greater than

13" WC. Check with your local gas utility or

supplier for availability of these delivery

pressures.

2.

Referring to TABLE 2, size supply piping to

keep flow capacity to the unit above 250 cubic

feet per hour (CFH) per unit installed.

3.

Run gas supply line in accordance with all

applicable codes.

4.

Locate and install manual shutoff valves in

accordance with state and local requirements.

5.

Install drip leg and ground joint union

(see Figure 5).

6.

All threaded joints should be coated with piping

compound resistant to action of liquefied

petroleum gas.

7.

The 9600 HWG unit and its individual shutoff

valve must be disconnected from the gas supply

Table 2. Gas supply piping.

Advertising