Shut off the manual gas valve, and call the unit for

heat. Main gas valve will be energized, attempting

to light, for four (4) seconds, and then will de-

energize. The unit will go into lockout after the

required number of trial for ignition periods.

Press the manual reset button on the boiler control,

or the user display, open the manual gas valve and

allow the unit to light. While the unit is operating,

close the manual gas valve and ensure that power to

the main gas valve has been cut.

13. Within three (3) days of start-up, recheck all air

bleeders and the expansion tank as described in

Steps 4 and 8 above.

WARNING

Improper adjustment may lead to poor combustion

quality, increasing the amount of carbon monoxide

produced. Excessive carbon monoxide levels may

lead to personal injury or death.

2.2 Shutting Down Mascot II

1. Turn off the main electrical disconnect switch.

2. Close all manual gas valves.

3. If freezing is anticipated, drain Mascot II and be

sure to also protect building piping from freezing.

All water must be removed from heat exchanger

and condensate trap or else damage from freezing

may occur.

This step to be performed by a qualified service person.

2.3 To Restart Mascot II

If drained, please refer back to section 2.1 of

this manual before restarting.

1. Turn off the main electrical disconnect switch.

2. Close all manual gas valves.

3. WAIT FIVE (5) MINUTES.

4. Set the aquastat or thermostat to its lowest setting.

5. Open all manual gas valves.

6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).

7. Switch on electrical power.

8. Burner will go through a prepurge period and

ignitor warm-up period, followed by ignition.

WARNING

Do not use this boiler if any part has been under

water. Immediately call a qualified service technician

to inspect the boiler and to replace any part of the

control system and any gas control which has been

under water.

WARNING

Should overheating occur or the gas supply fail to

shut off, do not turn off or disconnect the electrical

supply to the pump. Instead, shut off the gas supply

at a location external to the boiler.

FOR SERVICE

Contact your installing contractor, gas utility, Laars

dealer, or call Laars for the nearest authorized

representative in your area.