LAARS Mascot ll LMC - Users Manual User Manual

Page 6

Advertising
background image

LAARS Heating Systems

Page 6

3.2 Ignition Control- Sequence of Events

1. Call for heat

2. Safety chain check

3. Fan starts.

4. Prepurge timer is started.

5. Pre ignition time of 2 seconds to check the flame

sensor operation and status.

6. Trial for ignition period, 4 seconds. The direct

spark ignition switches to constant spark for three

seconds, during which time the gas valve is open.

For the last second of the ignition period direct

spark is de-energized and the flame sensor checks

for established flame. If flame is sensed the control

enters “Run” to satisfy the demand. If flame is

not established the control enters a retry, starting

from step 2. If flame has not been established in

the appropriate number of retries the control will

lockout with a 109 error code.

7. Call for heat complete

8. Gas valve off

9. Fan and pump over run times active to purge the

system
The sequence is the same for DHW or Central

Heat modes. Upon a call for Central Heat, the 3-way

valve will shift position, allowing boiler water to enter

the building’s heating loop. Only after the value shifts

position will the firing sequence begin.

3.3 Modulation Control

The control uses a PID algorithm to adjust

the firing rate of the boiler as the control point is

approached. The goal of the control is to operate

at a minimum firing rate to match the load on the

appliance. The burner modulates to achieve the setpoint

temperature, away from the actual off point.

3.4 Pump Control

The boiler pump is active anytime there is a call

for heat applied to the control. When there is a central

heat call supplied the system pump relay is active. If

there is a DHW call supplied while the central heat

call is active the system pump turns off. This happens

because of domestic hot water priority, which forces

the control to satisfy the domestic water demand prior

to the hydronic demand. When the last heat demand is

satisfied the boiler pump enters an overrun time.

3.5 High Limit

The control uses a dual thermistor sensor to

monitor the Mascot II’s maximum temperature. The

high limit sensor is installed in the outlet water. A dual

thermistor sensor is used, so that the two temperatures

can be monitored and compared to confirm accuracy.

The control will automatically reduce the firing of the

Mascot II to prevent the high limit from tripping. The

high limit setpoint is not adjustable.

3.6 Stack Temperature

The stack temperature is a dual thermistor sensor

and is limit rated. The control compares each of the

temperature readings to determine accuracy. The stack

sensor is used as a limiting feature to avoid excessive

temperatures in the venting.

3.7 Domestic Hot Water Temperature

The domestic hot water temperature sensor is used

to control DHW temperature. The DHW setpoint can be

adjusted through the USER menu structure.

DHW setpoint is displayed during DHW mode. For

LMH model, an aquastat will be used in lieu of a sensor

to control temperature of an indirect tank.

Caution

Scalding Risk: Laars recommends the use of a

thermostatic mixing valve at domestic hot water

outlet (boiler location) to reduce potential for

scalding.

The following thermostatic mixing valve model has been

tested and approved for Mascot II application: Honeywell

AM100-US-1. Contact Laars for additional recommended

models.

Advertising