Digital display and control – LAARS Mascot ll LMC - Users Manual User Manual

Page 5

Advertising
background image

User’s Manual - Mascot II Boilers and Water Heaters

Page 5

Figure 3. The User Interface.

The Mascot II has an integrated electronic control

that replaces many of the individual component controls

found on older appliances. The control acts as the

ignition control, pump control, high limit and cascading/

lead lag control and more. All of these functions and

setups are managed through the Digital Display.

3.1 Digital Display Navigation

The Digital Display is centered in the middle

of the User Interface and has 3 seperate modes of

control. They are USER, SETUP and DIAGNOSTIC.

The names of these modes gives you an idea of the

levels of control. A USER might be the homeowner or

a service technician. SETUP displays all the controls

needed when setting up or expanding the boiler. And

DIAGNOSTIC is intended for a Mascot ll trained

technician. Please view

Table 1, Table 2, and Table 3

.

USER Mode is the home screen shown on the

control. If the display is not in USER Mode wait for the

display timeout period to be reached or press the Done

button to return to the USER Mode.

SETUP Mode is accessed by holding the up and

down arrow keys simultaneously for 3 seconds.

DIAGNOSTIC Mode can be activated by a trained

Mascot II technician.

Once in a particular menu structure, navigation

consists of pressing the next button to scroll from item

to item and then pressing the up and down arrows to

change values. Once the value is adjusted, the NEXT or

DONE button can be pressed.

MENU ITEM

DEFINITION

F or C

Selects temperature units

LBTHODLOD Outdoor reset enable/disable -

enables menu items

LBT

Low boiler setpoint during outdoor reset

HOD

High outdoor temperature setpoint

LOD

Low outdoor temperature setpoint

RMT Add

Used for Lead/Lag (follow menus)

LL

Lead/Lag enable/disable - enables menu items

HS

Hysteresis - temp range between on/off cycles

bL

Base Load % - input rate before next boiler fires

Sd

Warm weather shut-down temperature

ASC

Anti short cycle - minutes of delay between

startup
bAC

Future use - Press DONE to exit menu.

PAS

Future use - Press DONE to exit menu.

NOTE:

When enabling/disabling functions, select "Done" and wait 30

seconds before scrolling.

Table 2. SETUP Mode Parameters.

MENU ITEM

FUNCTION

RANGE

DEFAULT

Outlet water Displays the current outlet 55-180°F 120°F

temperature water temperature & allows

the setpoint to be adjusted

Inlet water

Displays the current inlet

temperature water temperature
Delta T

Displays the current

temperature rise across

the heat exchanger

DHW

Domestic Hot Water

Caution

Stack

Displays the current stack

temperature temperature
Outdoor

Displays the current outdoor

temperature air temperature
Firing Rate Displays an indicator of the

current firing rate based

upon fan RPM. The actual

firing rate may vary.

Table 1. USER Mode Menu.

MENU ITEM

DESCRIPTION

Please view your Install/Operating Manual

Table 3. DIAGNOSTIC Mode Menu.

3. Digital Display and Control

Caution

Scalding Risk: Laars recommends

the use of a thermostatic mixing

valve at domestic hot water

outlet (boiler location) to

reduce potential for scalding.
The following thermostatic mixing

valve model has been tested and

approved for Mascot II application: Honeywell AM100-

US-1. Contact Laars for additional recommended models.