LAARS Mighty-Stack TL80-199 - Installation, Operation and Maintenance Instructions User Manual

Page 8

Advertising
background image

LAARS Heating Systems Company

Page 8

• When the water heater and a boiler are to be

connected to the same chimney, each unit must

have its own vent connector. The two connectors

must enter the chimney at least 6" (152 mm)

apart.

(a) Vent Connections

Use type B double wall or type C single wall gas

vent pipe (26 gauge, minimum thickness) from the

water heater to the chimney. Laars recommends

installation of a riser with a minimum of 12" (305

mm) height above the water heater. The vent system

should be sloped up toward the chimney at a rate of 1/

4" per foot (1 cm per 50 cm). The vent connector must

be strong enough to support the weight of the material

used. This will maintain the clearances and prevent

physical damage and separation of the joints.

NOTE: Always provide a minimum clearance of

6 inches (152 mm) between a Type C vent pipe and

any combustible materials.

Warning

Single-wall vent pipe must never pass through
interior walls, or through floors or ceilings! Failure to
comply with this warning could result in a fire,
causing property damage, personal injury, or death!

When installing the vent system, all applicable

national and local codes must be followed! If you

install thimbles, firestops or other protective devices,

and they penetrate any combustible or noncombustible

construction, be sure to follow all applicable national

and local codes.

If a vertical vent is installed, follow the code

requirements for Category 1, Fan Assisted

Appliances. Follow the requirements as indicated in

the latest edition of ANSI Z223.1/NFPA 54. See

“Sizing of Category I Venting Systems” and

“Appendix G.” In Canada, follow the instructions in

the CAN/CGA-B149 installation code.

An unused chimney can be used as a raceway for

a single-wall vent pipe (see Figure 7). Never run a

vent pipe through a flue that has another appliance

attached to it.

(b) Vent Termination

A listed vent terminal must complete the vertical

run where it exits the chimney. This must be designed

for the type of pipe being used. The vent pipe must

extend at least 3 feet (1 m) above the highest point

where it passes through the roof. In addition, the vent

cap must be at least 2 feet (0.6 m) higher than any part

of a building within a horizontal distance of 10 feet

(3m). Clearance to any combustible materials must be

maintained as listed (see Figure 8).

1L. Horizontal Venting – Category III

When a vent system is horizontal or cannot meet

the requirements of Category I, it can develop positive

pressure. This type of system must be installed in

accordance with the instructions in this section, and

with the instructions supplied by the vent

manufacturer.

(a) Vent Connections

The vent system must be gas tight. All seams

and joints must be sealed with silicone sealant or

adhesive tape having a minimum temperature rating of

400°F (204°C). (See Table 6 for a list of approved

sealing materials.)

Figure 7. Vertical Venting.

Figure 6. Chimney Venting.

Advertising