LAARS Mighty-Stack TL80-199 - Installation, Operation and Maintenance Instructions User Manual

Page 9

Advertising
background image

Mighty Stack Water Heater

Page 9

Figure 9. Horizontal Venting.

Outside wall

Vent

system

Water

heater

Thimble

Boiler venting detail

Caulk entire joint

including the screws

Sheet metal

screws

*12" Min.

(305 mm)

* When horizontal run
exceeds 5 ft. (1.5 m)

Figure 8. Vertical Vent Termination.

For best results, a horizontal vent system should

be as short and straight as possible. The materials

used in the vent connectors should be as listed in

Table 7.

Description

Manufacturer

Product

High Temperature

RTV

Dow Corning

Trade Mate

2" (51 mm) wide

aluminum foil tape,

Venture

Product #3243

backed with adhesive

2" (51 mm) wide

aluminum foil tape

3M

Product #433

backed with adhesive

Table 6. Vent Sealing Material.

In USA:

Up to a maximum of

Use UL type 304, 316 or

40 feet (12 m) of equiv-

29-4C stainless steel,

alent pipe run (including

26 gauge minimum.

required elbows).

In Canada:
Use “BH” vent type
complying with ULC
S-636 Standard.

Table 7. Vent Connector Materials.

The water heater vent collar must be fastened to

vent pipe of the same diameter, with rustproof metal

screws no longer than 1/2" (13 mm) and sealed with

high temperature 500°F (260°C) silicone sealant. For

larger diameter vent pipes, use a sealed reducer

fastened directly to the water heater collar and seal all

joints as indicated in Figure 9. Allow the sealant to

cure for 24 hours before operating the water heater.

The entire vent system must not exceed the size

specified in Table 8.

The following criteria must be observed:

• Attach a vertical pipe at least 12 inches (305

mm) high to the water heater outlet before the

horizontal run if run exceeds 5 feet (1.5m)

(see Figure 9).

• Support the vent run at 3-foot (1 m) intervals

with overhead hangers.

• Pitch down the vent run, toward the vent

terminal (hood), at a rate of 1/4 inch per foot

(1cm per 50 cm).

• Do not locate any joint screws at the bottom of

the vent run.

No. of

Horizontal Run

Diameter

Elbows

Length*

4" (102 mm)

4

20' (6 m)

*For each elbow eliminated, add 5 feet (1.5 m) of allowable vent.

Table 8. Horizontal Venting Configuration.