Locate the vent terminal so that it cannot be

blocked by snow. Most codes requires termination of
at least 12" (305mm) above grade, but the installer
may determine it should be higher depending on local
conditions.

1H-3. Common Venting System
When an existing boiler is removed from a

common venting system, the common venting system
is likely to be too large for proper venting of the
appliances remaining connected to it.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system
are not in operation.

1.

Seal any unused openings in the common
venting system.

2.

Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion or
other deficiencies which could cause an unsafe
condition.

3.

Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any gas burning appliance not connected to
the common venting system. Turn bathroom
exhausts, so they will operate at maximum

Figure 8. Horizontal Vent Termination.

3.

Pitch down the vent run, toward the vent terminal
(hood), 1/4" per foot (20mm per meter).

4.

Do not locate any joint screws at the bottom of
the vent run.

(b)

Vent Termination

The side wall vent terminal (hood), Laars Part

Number D2004300 (4") or D2000401 (6"), must be
used when the boiler is vented through a side wall. It
provides a means of installing vent pipe through the
building wall, and must be located in accordance with
ANSI Z223.1/NFPA 54, or in Canada CAN/CGA-
B149 and local applicable codes, (see Figure 8 ).

3 (0.9)

MIN.

VENT TERMINAL

VENT TERMINAL

FORCED

AIR INLET

GRADE

SHEET METAL

SCREWS

THIMBLE

ANCHORED

FASTENER

CAULK JOINTS

SEAL ENTIRE

CIRCUMFERENCE

OF JOINT

ANCHORED

FASTENER

CAULK JOINTS

EXHAUST

HOOD

VENT TERMINAL DETAIL

Figure 7. Horizontal Venting.

4 (1.2)

MIN.

4 (1.2)

MIN.

12 (3.7)

MIN.

VENT

TERMINAL

6 (1.8) MIN.

LESS THAN

10

(3.0)

Dimensions in
feet (m).

OUTSIDE WALL

VENT

SYSTEM

SHEET METAL

SCREWS

THIMBLE

BOILER

12" (305mm)

MIN.

BOILER VENTING

DETAIL

CAULK ENTIRE

JOINT, INCLUDING

THE SCREWS

*WHEN HORIZONTAL RUN

EXCEEDS 5 FT. (1.5m)

VENT TERMINAL

HOOD

*