1c. heater identification, 1d. flow requirements, 1a. introduction – LAARS Mini-Therm JVi - Install and Operating Manual User Manual

Page 4: 1b. warranty

Advertising
background image

Mini-Therm JVi

Page 3

Size

15°F 8°C

20°F 11°C

25°F 14°C

Flow Rate

Headloss

Flow Rate

Headloss

Flow Rate

Headloss

gpm

l/s

ft

m

gpm

l/s

ft

m

gpm

l/s

ft

m

50

5.3

0.3

0.3

0.1

4.0

0.3

0.2

0.1

3.2

0.2

0.1

0.0

75

8.0

0.5

0.6

0.2

6.0

0.4

0.3

0.1

4.8

0.3

0.2

0.1

100

10.7

0.7

1.3

0.4

8.0

0.5

0.7

0.2

6.4

0.4

0.5

0.2

125

13.3

0.8

2.2

0.7

10.0

0.6

1.3

0.4

8.0

0.5

0.8

0.2

160

17.0

1.1

2.5

0.8

12.8

0.8

1.8

0.5

10.2

0.6

1.2

0.4

225

24.0

1.5

5.0

1.5

18.0

1.1

3.1

0.9

14.4

0.9

1.9

0.6

is printed on the back cover of this manual. The owner
should fill out the warranty registration card and
return it to Laars.

All warranty claims must be made to an

authorized Laars representative or directly to the
factory. Claims must include the boiler serial number
and model (this information can be found on the
rating plate), installation date and name of the
installer. Shipping costs are not included in the
warranty coverage. Some accessory items are shipped
in separate packages. Verify receipt of all packages
listed on the packing slip. Inspect each item for
damage immediately upon delivery, and advise the
carrier of any shortages or damage. Any such claims
should be filed with the carrier. The carrier, not the
shipper, is responsible for shortages and damage to
the shipment whether visible or concealed .

1C. Heater Identification

Consult the rating plate on the boiler. The

following example simplifies the heater identification:

1

2

3

4

5

6

JV

H

125

N

C

S

Table 1. Heater Identification.

1.

Basic boiler series model

2.

Ignition system:

(H) Hot surface pilot ignition

3.

Input rate X 1000 BTU/Hr

4.

Gas Type: (N) Natural (P) Propane

5.

Firing rate: (C) On/off, induced draft

6.

Options: (S) Standard, (P) with Pump,
(A) Extra Aquastat

1D. Flow Requirements

All high recovery, low volume water boilers

must have adequate flow for proper operation. Pump
selection is critical to this goal, and pumps should be
selected to provide for correct system design water
temperature rise. Table 2 details temperature rise and
water flow for the Mini-Therm boilers.

SECTION 1.
General Information

WARNING

The JVi induced draft hydronic boiler must be
installed in accordance with the procedures detailed
in this manual, or the Laars warranty will be voided.
The installation must conform to the requirements of
the local jurisdiction having authority, and, in the
United States, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1. In Canada, the
installation must conform with the latest edition of
CAN/CGA B149.1 OR .2 installation codes for gas
burning appliances, and/or local codes.
Any modifications to the boiler, its gas controls, gas
orifices, wiring or draft inducer assembly may void
the warranty. If field conditions require
modifications, consult the factory representative
before initiating such modifications.

1A. Introduction

This manual provides information necessary for

the installation, operation, and maintenance of the
Laars Model JVi induced draft, low pressure, copper
tube hydronic boilers. These boilers are available in
two configurations; the JVH has a hot surface pilot
ignition system and the JVP has an electronic
intermittent ignition device (I.I.D.). Look for the
model designation on the rating plate, which can be
found on top of the boiler.

All application and installation procedures

should be reviewed completely before proceeding
with the installation. Consult the Laars factory, or
local factory representative, with any problems or
questions regarding this equipment. Experience has
shown that most operating problems are caused by
improper installation.

1B. Warranty

The Laars Model JVi induced draft boilers are

covered by a limited warranty. A copy of the warranty

Table 2. Temperature Rise (degrees °F, degrees °C).

gpm = Water Flow in gallons per minute.

l/s = Water flow in liters per second.

ft = Pressure drop (headloss) through the boiler in feet of water.

m = Pressure drop (headloss) through the boiler in meters of water.

Note: Shaded area is the recommended flow and temperature rise.