LAARS Heating Systems

Page 20

TURN GAS ON.

PILOT BURNER LIGHTS?

MAIN VALVE OPENS?

SYSTEM OK

IGNITER WARMS UP

AND GLOWS RED

PILOT VALVE

OPENS

START

TURN GAS SUPPLY OFF

SET THERMOSTAT TO

CALL FOR HEAT

SV9501/SV9601 IS

POWERED

(24 VAC NOMINAL)

YES

CHECK:

• LINE VOLTAGE POWER

• LOW VOLTAGE TRANSFORMER

• LIMIT CONTROLLER

• THERMOSTAT

• WIRING

• FAN PROVING SWITCH

ON COMBUSTION AIR BLOWER

UNPLUG IGNITER

MEASURE VOLTAGE AT

TWO BOTTOM TERMINAL OF

SV9501/SV9601

(24 VAC NOMINAL)

YES

YES

YES

YES

YES

NO

NO

NO

YES

NO

NO

NO

Troubleshooting Honeywell SV9501/SV9601

Hot Surface Pilot System

REPLACE IGNITER

REPLACE SV9501/SV9601

MEASURE VOLTAGE TO

SV9501/SV9601.

VOLTAGE MUST BE AT LEAST

19.5 VAC.

REPLACE IGNITER

REPLACE IGNITER SENSOR AND

RETAIN: RESTART TROUBLE-SHOOTING

SEQUENCE. DOES MAIN VALVE OPEN?

DISCARD OLD IGNITER SENSOR

NO

NO

NO

REPLACE

SV9501/

SV9601

CHECK

TRANS-

FORMER,

LINE VOLT

SUPPLY

REPLACE

SV9501/

SV9601.

SAVE OLD

IGNITER-

SENSOR

FOR

SERVICE.