6)

Lateral venting should slope upwards towards the chimney not less than one inch in four feet. No portion of vent pipe

should run downward or have sags. Vent pipe must be securely supported.

7)

The connector rise coming off the boiler should be as tall as possible, while still maintaining the proper
clearance from the horizontal vent connector to combustibles and the proper pitch called for in (6) above.

8)

Lateral vent pipe should be installed above the bottom of the chimney to prevent blockage.

9)

Lateral vent pipe must be inserted flush with inside face of the chimney liner and the space between vent pipe and
chimney sealed tight.

24

Table 4: Sizing For Vent Systems Outside The Scope Of The National Fuel Gas Code Venting Tables

IMPORTANT: READ THE ENTIRE VENT SECTION

AND REFER TO FIGURE 20 BEFORE
ATTEMPTING TO USE THIS CHART

32-475*
32-570

20

9 1/2

12

32-665

20

9 1/2

12

32-760

20

10

12

32-855

20

10 1/2

12

32-950

20

11

14

32-1045

20

11 1/2

14

32-1140

20

12

14

32-1235

20

12 1/2

14

32-1330

20

13

16

32-1425

20

13 1/2

16

32-1520

20

14

16

32-1615

20

14 1/2

16

32-1710

20

14 1/2

18

32-1805

20

15

18

32-1900

20

15 1/2

18

32-1995

20

16

18

32-2090

20

16 1/2

18

32-2185

20

17

20

32-2280

20

17 1/2

20

32-2375

20

18

20

32-2470

20

18 1/2

20

32-2565

20

19

20

32-2660

20

19 1/2

22

32-2755

20

19 1/2

22

32-2850

20

20

22

* USE NATIONAL FUEL GAS CODE TO SIZE 32-475 VENTING

MODEL

MIN. COMMON VENT

INSIDE DIA. (D), in

MIN. CHIMNEY

HEIGHT (H), ft

MAX. LATERAL

COMMON VENT (Lm), ft