Crown Boiler 32 User Manual

Page 31

Advertising
background image

31

29

Table 5

Figure 22: Steam Boiler Tapping Locations

Tapping Uses Chart For Steam Boilers

1

Component Description

Tapping

Tapping

Standard

CSD-1

Location

Size (in)

Equipment

Package

Supply Piping

A

3

N

N

Return Piping

B

3

N

N

Safety Relief Valves

(With Inlet Opening Up To & Including 1-1/2" NPT Inlet)

Safety Relief Valves

(With Inlets Larger Than 1-1/2" NPT Inlet)

Y

Y

Pressure Gauge

D

1/2

Y

Y

Water Gauge Glass Fittings

E

1/2

Y

Y

M & M #67 Low Water Cut-Off

E

1/2

Y

N

M & M #67M Low Water Cut-Off with Manual Reset

E

1/2

N

Y

Hydrolevel CG450 Probe Low Water Cut-Off

G

3/4

N

Y

Steam Equalizer Installed On The End Not Equipped With Trim

Between

(With Optional M & M #150 Float Low Water Cut-Off / Pump Controller)

B & J

Honeywell PA404A Or L404A Pressure Limit

D

1/2

Y

Y

Boiler Drain Valve

B

3

Y

Y

Bottom Blowoff Piping

B

3

N

N

Cover Plate

F

-

Y

Y

Indirect Water Heater Connection

H

1-1/2

N

N

Indirect Water Heater Aquastat

I

3/4

N

N

1. Trim May Be Installed On Either End Section.
2. Use The Tapping Located On The End Not Equipped With Trim For The Safety Relief Valve & The Surface Blow off .

Honeywell L404C Manual Reset Pressure Limit Control

N

Y

C

2

Y

Y

N

N

1-1/2

-

1/4" Tapping on

Top of #67 LWCO

-

3 & 1

Riser

(See Figure 27c)