Bfc36 balance flue heat-circulating fireplace, Side wall protection, Hearth installation – Vermont Casting 647 BFC User Manual

Page 15: Minimum wall clearances, Minimum hearth extension dimensions

Advertising
background image

15

BFC36 Balance Flue Heat-Circulating Fireplace

7412647

Side Wall Protection

Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 24 of the fireplace
opening must be protected with CFM Corporation Wall
Shield Model SP40 or a specifically built wall shield
described in Figure 18.
The special wall shield design described in Figure 18 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.
Examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. EH2416, K = .458,
1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 21 for mini-
mum dimensions and mounting detail.
Note: Hearth Extension must not cover the air inlet
opening of a fireplace.
The hearth extension described in Figure 21 must be
a durable non-combustible material with a minimum
(total) Rt value of 1.09; refer to Figure 22 for examples.
The overall height (above a combustible floor), depth
and width must be as indicated, with the extension cen-
tered to the fireplace opening.
The top of insulation must be covered with a non-com-
bustible decorative covering or a piece of .018” mini-
mum sheet metal, to protect hearth extension material.
(Fig. 21)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a non-combustible
material. (Figs. 21 and 23)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the

fireplace

and hearth

extension with

noncombustible

material

Safety strips

must overlap

���

" minimum

May install

noncombustible

decorative

covering

OR .018" min.

sheet metal

Fireplace

Hearth

Combustible

Floor

Minimum

Insulation

Value "R"

4" MIN.

FP594b
BFC combustible min.
8/21/00 djt

Firebox

Opening

A - Min. clearance

to combustible

perpendicular wall

B - Min. clearance

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F**

C**

E

E

D

4" Brick

(Example material)

Combustible material permitted within shaded area.

* Noncombustible wall shield requires 1" EH2416

insulation (minimum R Value = 1.85) between decorative

noncombustible rigid covering and combustible wall.

Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness

of noncombustible surround facing.

Shaded area

starts 1/2" from

away from edge

of unit 4"

FP594b

Fig. 21 Combustible side wall protection and hearth extension dimensions.

A

B

C

D

E

F

G

H

J

BFC36

26”

12”

17°

25°

12”

8”

8”

18”

47¹⁄₄”

660mm 305mm

3085mm 203mm 203mm 457mm 1200mm